Hitachi CHL-MBS-02 Installation And Operation Manual page 11

Modbus gateways
Hide thumbs Also See for CHL-MBS-02:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 8
INSTALLATION
3.6 INSTALLATION PROCEDURE
!
D A N G E R
Do not install this device in places accessible to the general pub-
lic. Install it in enclosures or other places which are accessible
only by the usage of a tool.
Do not connect power supply before the device installation is
correctly done. Always disconnect power supply from the device
before any maintenance or servicing action
!
C A U T I O N
Check to ensure that the field supplied electrical components (mains
power switches, circuit breakers, wires, connectors and wire termi-
nals) have been properly selected according to the electrical data indi-
cated on this document and they comply with national and local codes
3.7 NETWORK CONFIGURATION
It is supplied a computer software tool, Net configuration
Tool, inside the USB stick memory for an easy and friendly
configuration.
3.7.1 Computer requirements.
It is required to use a personal computer with Microsoft Windows
7 or higher, a free USB port and Java.
3.7.3 Configuration procedure

Configuration through USB port
This method is required when the device IP is unknown.
1 Connect the network device to a computer by a USB cable (field supplied or available with the Net Configuration Kit)
2 Select the communication port of the computer.
3 Press the
button at screen
5
PMML0302A rev.2 - 11/2015
Any unit that is not connected or is not under power when turning on
Modbus gateways, will not be recognized and will have to be config-
ured later.
-
Before power supply and turning on the Modbus
gateways, you must ensure that:
Š 1. All circuits to be connected are correctly applied.
Š 2. All H-Link connections have been set up.
Š 3. Modbus connection has been properly done.
The signals' cables should be as short as possible. Keep a distance of
more than 150 mm from other power cables. Do not wire them together
(although they may intersect). If they must necessarily be installed to-
gether, take the following measures to avoid noise disturbances:
-
For communications, use shielded wire which is earthed
at one side.
3.7.2 Parameters under configuration:
-
Parity: Odd/Even/Disabled
Communication speed: 9600/19200 Bps
-
-
Modbus address
-
Modbus TCP IP

Advertisement

Table of Contents
loading

This manual is also suitable for:

8e500021

Table of Contents