Line connection conditions for the converter with the motor 1FL2

Description
The drive system is designed for connection to grounded TN/TT and non-grounded IT mains
supply networks.
Depending on the motor/converter combination and the planned installation altitude, the
following constraints must be taken into account regarding the line connection.
Table 4-2
Line connection conditions for the converter with the motor 1FL2
Motor
Converter input
voltage
200 V
1 AC 200 V ... 240 V
(-15% ... +10%)
200 V
3 AC 200 V ... 240 V
(-15% ... +10%)
400 V
3 AC 380 V ... 480 V
(-15% ... +10%)
With the IT screw for the functional grounding removed. For more information about
*)
removing the IT screw, see Section "Removing the IT screw for the functional grounding
(Page 84)".
NOTICE
Damage to motor insulation due to excessive voltages
In the event of a ground fault in the IT supply system, the motor insulation can be damaged by
the higher voltage to ground.
• Use a ground fault monitor.
• Eliminate the ground fault as quickly as possible.
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB
4.4 Line connection conditions for the converter with the motor 1FL2
Permissible line system configurations
for installation altitude no higher
than 2000 m
TN and TT line systems with grounding
at any potential
IT line systems
*)
TN and TT line systems with grounding
at any potential
IT line systems
*)
TN and TT line systems with grounded
neutral point
IT line systems
*)
Application planning
Permissible line system configurations for in‐
stallation between 2000 m and 4000 m
Install an isolating transformer and ground the
secondary side at any potential.
TN and TT line systems with grounded neu‐
tral point
IT line systems with an isolating transformer
with grounded neutral point (secondary
side)
Install an isolating transformer and ground the
secondary side at the neutral point.
83