4.4
Line connection conditions for the converter with the motor 1FL2
Description
The drive system is designed for connection to grounded TN/TT and non-grounded IT mains
supply networks.
Depending on the motor/converter combination and the planned installation altitude, the
following constraints must be taken into account regarding the line connection.
Table 4-2
Line connection conditions for the converter with the motor 1FL2
Motor
Converter input
voltage
200 V
1 AC 200 V ... 240 V
(-15% ... +10%)
200 V
3 AC 200 V ... 240 V
(-15% ... +10%)
400 V
3 AC 380 V ... 480 V
(-15% ... +10%)
With the IT screw for the functional grounding removed. For more information about
*)
removing the IT screw, see Section "Removing the IT screw for the functional grounding
(Page 84)".
NOTICE
Damage to motor insulation due to excessive voltages
In the event of a ground fault in the IT supply system, the motor insulation can be damaged by
the higher voltage to ground.
• Use a ground fault monitor.
• Eliminate the ground fault as quickly as possible.
SINAMICS S200 PROFINET servo drive system with SIMOTICS S-1FL2
Operating Instructions, 11/2023, FW V6.3, A5E51646752B AB
4.4 Line connection conditions for the converter with the motor 1FL2
Permissible line system configurations
for installation altitude no higher
than 2000 m
•
TN and TT line systems with grounding
at any potential
•
IT line systems
*)
•
TN and TT line systems with grounding
at any potential
•
IT line systems
*)
•
TN and TT line systems with grounded
neutral point
•
IT line systems
*)
Application planning
Permissible line system configurations for in‐
stallation between 2000 m and 4000 m
Install an isolating transformer and ground the
secondary side at any potential.
•
TN and TT line systems with grounded neu‐
tral point
•
IT line systems with an isolating transformer
with grounded neutral point (secondary
side)
Install an isolating transformer and ground the
secondary side at the neutral point.
83