Installation
4 Way Cassette
Level
7 Adjust the unit to the appropriate position, taking into
account the installation area for the front panel.
• Place the pattern sheet on the indoor unit.
• Adjust the space between the ceiling and the
indoor unit by using a Tape measure.
• Fix the indoor unit securely after adjusting the level
of the unit by using a level.
• Remove the pattern sheet and install the front
panel.
When the installation template is made of paper
4 way Cassette
Indoor unit
0.67 inch (17 mm)
0.79 inch (20 mm)
Ceiling
Gauge of dimensions
Installing the drain hose and drain pipe
1 Push the supplied drain hose as far as possible over
the drain socket.
2 Tighten the metal clamp as shown in the picture.
3 Wrap the supplied large sealing pad over the metal
clamp and drain hose to insulate and fix it with clamps.
4 Insulate the complete drain piping inside the building
(field supply).
If the drain hose cannot be sufficiently set on a slope,
fit the hose with drain raising piping (field supply).
5 Push the drain hose up to insulation when connecting
the drain hose to drain socket.
4 way Cassette
Metal clamp
Large sealing pad
Drain hose
Drain socket
Drain hose
Drain pipe
Be sure to bond the drain
hose and the main pipe.
PVC Tube Joint
+VP25 (OD: 1.26 inch (32 mm), ID:
0.98 inch (25 mm))
Drain pipe