5. Function Menu Screen Display

5.12 FrostWash

Frostwash is a function that freezes and frosts the heat exchanger inside the air conditioner, then rapidly melts
accumulated frost to flush away dirt. This keeps the unit in a clean status and also helps prevent performance
degradation due to dust clogs. (*)
FrostWash can only operate when all air conditioning are stopped. As a feature, Auto-FrostWash or Manual
FrostWash are selectable.
(*)FrostWash may not eliminate all dirt, mold, or similar substances.
NOTES:
This function cannot be set when the indoor unit and the outdoor unit do not support this function.
When the air conditioner system supports FrostWash function and the function selection F1 of outdoor unit
is set, then the FrostWash is automatically enabled.
Depending on the outdoor unit, the settings on the outdoor unit may be required.
Cracking noise may be heard during freezing or defrosting phase due to temperature change. Refrigerant
flow noise may also be heard. The noise may be heard relatively louder in a quiet environment. It is
recommended to set "Auto-FrostWash Schedule" when room is not occupied.
In humid environments, it is possible that during the FrostWash cycle mist may be discharged from the
supply air grille. This is normal.
The FrostWash cycle can operate only when the outdoor temperature is between 1°C and 43°C and the indoor
temperature is between 15°C and 30°C.
The level of dust removed depends on usage environment. In dusty environments, the FrostWash cycle may
need to be run more frequently.
Limitations and settings are required when using this feature in a VRF system. For more information, please
refer to the outdoor unit service manual for FrostWash function.
5.12.1 Function
(1) [Function 1] Auto-FrostWash
Automatically runs the FrostWash cycle after the indoor unit has been operated for the present number of
hours and the unit is turned off.
Auto-FrostWash Flow
*1: Advanced wired controller can set 50-400 hours.
Cooling or
last FrostWash
other mode
Operate
Auto-FrostWash is initially disabled in the default setting. To enable this feature, follow the outdoor unit
installation manual and configure it using function selection F1.
If the Auto-FrostWash is interrupted, the total operating time will be reset.
(2) [Function 2] Manual FrostWash
This function allows the FrostWash feature to be run at any time.
5.12.2 Advanced Wired Remote Controller Setting Item
Start FrostWash ( Page 35 )
This item is selected when performing [Function 2] Manual FrostWash.
Manual FrostWash can be performed even if Auto-FrostWash is enabled.
Enable/Disable Auto-FrostWash (Page 36 )
[Function 1] This is a setting to enable or disable Auto-FrostWash.
○ "Enable": FrostWash is performed automatically.
○ "Disable": The function does not work (the default setting).
34
The total operating time is 100 hours*
(Default setting)
. . .
Cooling or
other mode
Stop
Operate
Start FrostWash
Approx. 3 min.*
Approx. 10 min. to 35 min.*
*2: Change according
*3: Change according to
to the outdoor unit.
indoor temperature
and outdoor temperature.
FrostWash
FrostWash
preparation
Stop
FrostWash Completed
Stop Automatically
A16381H9HL

Advertisement

Table of Contents
loading

This manual is also suitable for:

Pc-arfg2-z

Table of Contents