    USER MANUAL NI PXIe-7862 R Series Reconfigurable I/O Module (AI, AO, DIO) for PXI Express, 16 AI, 8 AO, 32 DIO, 1 MS/s AIO, 512 MB DRAM, Kintex-7 325T FPGA This document provides compliance, pinout, connectivity, mounting, and power information for the NI PXIe-7862.
  • Page 3 Pinout AI8- AI0+ 68 34 AI0– AI8+ 68 34 AIGND8 AIGND9 AIGND0 67 33 AIGND1 67 33 AI9+ AI9- AI1+ 66 32 AI1– 66 32 AI10+ 65 31 AI10- AI2+ 65 31 AI2– AIGND10 64 30 AIGND11 AIGND2 64 30 AIGND3 AI11+ 63 29...
  • Page 4: Connectivity Options

    RMIO Shielded Cable, 68 pin D- RMIO 189588-01 Type to 68 pin VHDCI (1 m) NI SHC68-68- RMIO RMIO Shielded Cable, 68 pin D- 189588-02 Type to 68 pin VHDCI (2 m) NI PXIe-7862 User Manual | © National Instruments | 3...
  • Page 5: Analog Input

    Analog Input The NI PXIe-7862 provides connections for 16 AI channels. Each channel has an AI+ pin, AI- pin, and AIGND pin to which you can connect both single-ended or differential voltage signals. Use the AISENSE pin to connect non-referenced single-ended signals. Connecting Single-Ended Voltage Signals To connect referenced single-ended voltage signals to the NI PXIe-7862, you must connect the voltage ground signal to AI GND in order to keep the common-mode voltage in the specified...
  • Page 6: Connecting Differential Voltage Signals

    NI PXIe-7862 Analog Output The NI PXIe-7862 provides connections for eight analog output channels. Each channel has an AO pin and AOGND pin to which you can connect a load. NI PXIe-7862 User Manual | © National Instruments | 5...
  • Page 7 Figure 6. Connecting a Load LOAD AOGND Connection NI PXIe-7862 Accessory Digital I/O The NI PXIe-7862 provides connections for 32 digital input/output (DIO) channels. Connector 0 and Connector 1 each contains 16 low-speed channels that can run up to 10 MHz signal frequencies.
  • Page 8: Field Wiring Considerations

    Never connect the +5 V power terminals to analog or digital ground or Caution any other voltage source on the NI PXIe-7862 or any other device. Doing so can NI PXIe-7862 User Manual | © National Instruments | 7...
  • Page 9: Worldwide Support And Services

    National Instruments is not liable for damage resulting from such a connection. The power rating is 4.75 to 5.1 V DC at 0.5 A per connector. Worldwide Support and Services The NI website is your complete resource for technical support. At ni.com/support, you have access to everything from troubleshooting and application development self-help resources to email and phone assistance from NI Application Engineers.