Parameters; The Following Mm440 Parameters Are Required To Be Entered; 2.1.1 Perform Quick Commissioning - Siemens LMV52 Series User Documentation

Hide thumbs Also See for LMV52 Series:

Advertisement

Indicates
status
Change
direction
Jog
motor
Access

parameters

Functions
Parameter
1
Start quick commissioning
Note: P0010 must always be set back to «0» before operating the motor. However, after commissioning
if P3900 = 1, this is done automatically.
2
Operation for Europe / US
3
Rated motor voltage
4
Rated motor current
5
Rated motor power
6
Rated motor frequency
7
Rated motor speed
8
Command source
9
Frequency setpoint
10
Min. motor frequency
11
Max. motor frequency
12
Ramp-up time
Note: The «Ramp-up time» must be the same value as the «Ramp-down time».
13
Ramp-down time
Note: For setting the «Ramp-down time», it is important to set a time that will not cause the drive to
fault with too high DC-link voltage (F0002 error).
«This can be achieved by monitoring the DC-link voltage displayed on the BOP / AOP».
Building Technologies Division
Industry Sector
2
Parameters
2.1 The following MM440 parameters are required
to be entered
The table below describes the functions of the key pad (BOP / AOP) on the front of the
MM440 Variable Speed Drive to enable the parameters to be entered.
The LCD displays the settings
currently used by the Variable
Speed Drive
Press this button to change
the direction of the motor
The LCD displays the settings
currently used by the Variable
Speed Drive
Pressing this button allows
access to the parameters
This button can be used to view additional information.
Pressing this button for 2 seconds will return to operating screen.
Quit: This button will reset a fault or alarm message on the BOP / AOP

2.1.1 Perform quick commissioning

No.
Setting
P0010
P0100
P0304
P0305
P0307
P0310
P0311
P0700
P1000
P1080
P1082
52.6
P1120
40
P1121
40
LMV52... with MM440 Variable Speed Drive
2 Parameters
Start motor
Stop motor
Increase
value
Decrease
value
Description
1
Quick commissioning
0
Frequency default 50 Hz
?
Nominal motor voltage (V) from rating plate
?
Nominal motor current (A) from rating plate
?
Nominal motor power (kW) from rating plate
?
Nominal motor frequency (Hz) from rating plate
?
Nominal motor speed (rpm) from rating plate
2
Terminal / digital inputs
2
Analog setpoint
0
Sets the minimum motor frequency
Sets the maximum motor frequency irrespective of set-
point
Time taken for motor to accelerate from standstill to
maximum motor frequency - (must be less than
LMV5...)
Time taken for motor to decelerate from maximum mo-
tor frequency to standstill - (must be less than LMV5...)
This button is disabled by default
setting - see P0700
This button is disabled by default
setting - see P0700
Pressing this button increases the
displayed value
Pressing this button decreases the
displayed value
CC1A7550.2en
20.05.2011
5/10