10.4.2.2
The parameter "Unit" determines the volume unit of the total volume counter. The
listed volume units are available. When changing the volume unit, the current
counter reading is converted to the new volume unit.
10.4.3
10.4.3.1
The displayed unit for the temperature measurement can be selected from
various default units. It is also possible to define a user-defined unit ("user"), in
which case the "user unit" must be programmed in °C.
e.g. Unit "user" = 50 °C, if T = 50 °C then the display shows 1 user.
10.4.3.2
See section 10.4.5
10.4.4
10.4.4.1
Absolute:
Regardless of the flow direction, the calculated partial volume is added to the
counters.
Bidirectional:
Depending on the flow direction, the calculated partial volume is added or
subtracted to the counters. If the measured flow value is negative, the volume
value goes down from measurement to measurement (possibly into the
negative range).
10.4.4.2
The parameter "unit" defines the volume unit of all volume meters. The listed
volume units are available. When changing the volume unit, the current counter
readings are converted to the new volume unit.
10.4.4.3
In this menu, the part quantity counter can be reset.
10.4.4.4
Simulation function
See section 10.4.5
10.4.5
With the simulation function, all available measured values can be simulated
independently of each other for a limited time. The simulated measured values
have full effect on the displays and outputs.
Each simulation started is automatically stopped after the time set in the "Sim
Auto Stop Time" (user service) parameter (1 to 30 min) or after the programmed
intervals have expired.
The following measured values can be simulated:
page 24
Unit of the total volume counter
Temperature
Temperature Unit
Simulation function
Part Volume
Counter type
Unit of the part volume counter
Memory reset
Simulation function