Hitachi air Core 600 Installation & Maintenance Manual page 6

Large single split inverter
Table of Contents

Advertisement

-
If the unventilated area is smaller than the minimum installation area, the air conditioner
should not be installed in this area.
-
The installation height is the minimum installation height, that is, the minimum installation
height of the cold air pipe or indoor unit, whichever is the lowest. The following table is
determined according to the minimum installation height of 1.8 meters and 2.2 meters
-
If the required minimum installation height is less than 1.8 meters, the minimum installation
space must be recalculated.
Minimum Room Size Table for installation (Amin)
The amount of refrigerant
to be filled (M) (kg)
M ≤ 1.224
1.224 < M ≤ 1.836
1.836 < M ≤ 2.448
2.448 < M ≤ 3.672
3.672 < M ≤ 4.896
4.896 < M ≤ 6.12
6.12 < M ≤ 7.956
Refrigerant packaging cost table (M max)
Minimum room area
(Amin) (m²)
Amin ≤ 4
4 < Amin ≤ 7
7 < Amin ≤ 10
10 < Amin ≤ 15
15 < Amin ≤ 20
20 < Amin ≤ 30
30 < Amin ≤ 50
1. Installation (area)
Installation area with minimal piping
Installation area to protect piping from physical damage
Installation area complies with national gas regulations
The installation area can be maintained using mechanical connections
If mechanical ventilation is required, the vents must not be blocked by anything.
To dispose of this equipment, it should comply with national regulations and operate
normally.
2. Maintenance
2-1. Maintenance Officer
Caution
Minimum room area (Amin) (m²)
Installation Height (ho) (m)
1.8
--
3.25
5.75
13.00
23.00
36.00
60.40
The amount of refrigerant filled (M) (kg)
Installation Height (ho) (m)
1.8
2.05
2.71
3.24
3.97
4.58
5.61
7.24
4
2.2
--
2.15
3.85
8.70
15.30
24.00
40.40
2.2
2.50
3.31
3.96
4.85
5.60
6.86
8.85