Original instructions HD5-B-901 (CustomerSolution) Three position enabling device with safe AS-i slave ABB AB JOKAB SAFETY, Varlabersvägen 11, SE-43439 Kungsbacka www.abb.com/lowvoltage...
PERFORMANCE DATA Due to the fact that efforts have been made to ensure the accuracy of the information contained in this manual, ABB JOKAB SAFETY assumes no responsibility for errors or omissions and reserves the right to make changes and improvements without giving notice.
Prerequisites It is assumed that the reader of this document has the following knowledge: • Basic knowledge of ABB JOKAB SAFETY products • Knowledge of the AS-i Bus system •...
If you have any questions regarding the existing configurations or the possibilities for a configuration adapted to your needs, please contact ABB JOKAB SAFETY. Application area The enabling device is used in machines and facilities to provide protection to people, who, because of their work (e.g.
(evaluate the signals) of the enabling device, allowing the product to be used the specified way. All liability is excluded if the instructions are not complied with, especially in cases of interference with or modifications to the product. 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...
When released, the three-position enabling switches always go back to position 1, regardless of whether they were in position 2 or 3. Notice on operation To ensure a correct and safe operation, the enabling button must be pressed in the middle with two fingers three fingers 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...
The controls for the feedback LED are independent from the emergency stop button function. The programmer is solely responsible for their signaling function. ABB JOKAB SAFETY does not accept any liability for damages of any kind caused by signaling that is not logical, and the resulting misjudgments and errors by users.
Additional buttons No. 3 and No. 4 These buttons are installed on the grey housing. They can be controlled in a user-defined way via the AS-i Bus. Additional labelling of the buttons is an option for custom configurations. 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...
Avoid looking directly into the lens of the assist light. Looking directly into the lens, and the glare effect which may result from this, can sometimes impair vision, which may cause irritation, adverse effects, or even accidents. 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...
AS-i (green) Fault (red) Description No power supply to AS-i Normal operation AS-i communication disrupted Flashing No data exchange because address = 0 alternating flashing alternating flashing Peripheral error Flashing Recognizes double addresses (ABB version only) 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...
AS-i cable by 12m per device Attention! Please note, if an emergency stop button is implemented in the enabling device and the connection becomes deconnected, additional measures can required, as described in Section 3 “Functional description, emergency stop button”. 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...
At mounting the specific holder “HD5-M-xxx” please ensure that the enabling device hang up completely in the holder. The Position should selected in view of ergonomic and safety relevant aspects. More Information in Section 10 “Accessories” 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...
Functional Test At first commissioning after installation, a functional test based on the application case must be carried out in accordance with current guidelines for the case of application and the relevant harmonized standards. 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...
Please get in touch with your regular contact for maintenance work or your nearest ABB JOKAB SAFETY customer service or dealer. Do not attempt to repair the product yourself. Any attempt to interfere with the device will result in a loss of warranty. There is also a possibility of the product becoming damaged, affecting its safety and how it functions, which may lead to serious injury.
The feedback LED integrated into the actuator cap of the emergency stop button or the enabling button housing also offers a range of different possibilities for signaling as part of its functions. Attention! You can find further explanations and warnings relating to the below functions in Section 3. “Functional description” 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...
9. Model overview HD5-B-xxx enabling device with integrated AS-i technology are described below. Custom versions • Type name: HD5-B-901 • Item number: 2TLA920502R0001 / 2TLA920502R0002 Position Function Additional information number Enabling button Emergency stop button Feedback LED integrated into emergency stop...
• high breaking strength • Resistant to almost all cleaning fluids • Shape created in accordance with hygienic design principles • Type name: HD5-M-002 • Item number: 2TLA920509R0002 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...
11. TECHNICAL DATA Manufacturer Address ABB AB JOKAB SAFETY Varlabergsvägen 11 SE-434 39 Kungsbacka Sweden Power supply Operational voltage 30 VDC, AS-i Bus, tolerance 26 - 31,6 VDC Overall power consumption <150 mA General Protection class IP65 Ambient temperature for during operation -10°C...
Page 23
< 43 ms (with setting „Disturbance immunity“) The response times refer exclusively to the AS-i monitor Pluto from the manufacturer ABB. When using an AS-i monitor from another manufacturer, the response times may differ. Further information on the profile and addressing, see chapter "AS-i configuration"...
Page 24
2006/42/EC – Machines, 2014/30/EU – EMC, 2011/65/EU – RoHS2, 2015/863-RoHS3 EN ISO 12100-1:2010, EN ISO 13849-1:2015, EN 62061:2015 EN 60204-1:2006 + A1:2009, SILCL 3 PL e, category UL/CSA 60947-5-1 UL/CSA 60947-5-5 only for variants with an E-Stop is included Certificates TÜV Süd AS-International Assoziation 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...
The following bit description relates to functions that are generally possible, and is set out in detail in the data sheet enclosed with the product (or available from ABB), depending on the configuration. Custom versions HD5-B-901 (up to 10 tuning devices may be used on one AS-i cable)
12. Dimensions All the dimensions are given in millimeters (mm) 3-position enabling device Device specified Holder 2CDC172114M0201 www.abb.com/lowvoltage 2019-09-06 V1.3...