Section 6
Connecting
Table 19:
No
1
2
3
4
5
Connect each signal connector terminal of screw compression type with one 0.5 to 2.5 mm
AWG 14) wire or with two 0.5 to 1.0 mm
Protective conductor terminal must be connected to the cubicle or station protective grounding system.
Electrical codes and standards require that protective ground cables are green/yellow conductors with a
cross section area of at least 2.5 mm
grounding system. Use a conductor with a core cross section area of at least 4 mm
REX061 Capacitor unit connections
Table 20:
No
1
2
3
4
5
6
7
8
9
10
Table 21:
No
1
2
3
X1 connector. Connect each signal connector terminal of screw compression type with one 0.14 to 6
2
mm
(AWG 35 - AWG 3) wire or with two 0.14 to 1.5 mm
X2 connector. Connect each signal connector terminal of screw compression type with one 0.5 to 2.5
2
mm
(AWG 24 - AWG 14) wire or with two 0.5 to 1.0 mm
64
Rotor injection connection X82
Injection (same as 3)
Injection, inside shunt resistor
Injection (same as 1)
Injection return (same as 5)
Injection return (same as 4)
Injection and rotor connection X1
Rotor positive pole
-
Positive pole
-
Negative pole
-
Rotor negative pole
-
Rotor injection
Injection ground. Internally connected to chassis and PE
Measurment connector X2
Rotor + voltage divided by 1 000
Ground
Rotor - voltage divided by 1 000
© 2017 - 2023 Hitachi Energy. All rights reserved
Signal
2
(AWG 24 - AWG 18) wires.
2
(AWG 14). The cubicle must be properly connected to the station
Signal
Signal
2
(AWG 35 - AWG 15) wires.
2
(AWG 24 - AWG 18) wires.
1MRK514026-UUS Rev. P
2
(AWG 24 -
2
(AWG 12).
670 series
Installation manual