General Description; Detector; Latching - Panasonic 6295 Manual

Enclosed heat detector
Hide thumbs Also See for 6295:
Table of Contents

Advertisement

6295-6298 ENCLOSED HEAT DETECTOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION

3. GENERAL DESCRIPTION

The heat detectors are conventional fixed temperature heat detectors. The detectors will give an alarm at a certain fixed tempera-
ture (57 °C / 72 °C / 87 °C / 117 °C).
The detector is intended for outdoor use or indoor use in high humidity premises.
(Measure in mm)

1. Detector

2. Connection box
3.1.
DETECTOR
The sensing element is a heat pick-up shield and a bimetal switch.
The detectors will give an alarm within a response temperature range in accordance with EN54-5, see table below.
Type
Static response temperature
6295
57 °C
6296
72 °C
6297
87 °C
9298
117 °C
3.1.1.

LATCHING

The detector is latching. The detector will not be automatically reset if the temperature, after the alarm, falls below the detector's
static response temperature. The detector's LED and a connected external LED will be lit until the detector is reset via the CIE.
75
95
1
2
Category
A2 S
B S
C S
E S
5
100