Technical Data 6298 - Panasonic 6295 Manual

Enclosed heat detector
Hide thumbs Also See for 6295:
Table of Contents

Advertisement

6295-6298 ENCLOSED HEAT DETECTOR - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION

10. TECHNICAL DATA 6298

All current consumptions are valid by nominal voltage and by 25 °C.
Voltage:
Allowed
Normal
Current:
Quiescent
Active
Current limitation required when active
Alarm resistance
Short circuit isolator
Internal battery
Material
Ambient temperature:
Operating
Storage
Static response temperature
Ambient humidity
Ingress protection rating
Size:
Ø x H
Weight:
Colour
12 – 30 V DC
24V DC (Zone line voltage)
0 mA
25 mA
Must be minimum 6 and maximum 30 mA
680 Ω
No
No
FR ABS and polycarbonate
-40 to +110 °C
-45 to +70 °C
117 °C
Maximum 95 % RH (Non condensing)
IP67
100 x 75 mm
82 g
Grey (N8, Munsell colour code)
15

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

6298

Table of Contents