6.6

Device Address

Setting a device address is not necessary for local operation, but must be set if configuring
the SITRANS LUT400 for use on a HART network. See Device Address (4.1.) (Page 264).
6.7

Testing the configuration

After programming the device, it is recommended that you test the device to ensure that it
performs to your specifications. This test can be run in simulation mode or by varying the
actual level in the application. The latter is preferred as it more accurately represents running
conditions. However, if it is not possible to do a physical test, a simulation will ensure that
control programming is correct. For further details, see Pump relay behaviour during
simulation (Page 156), and Application test (Page 159).
6.8

Application examples

In the examples that follow, substitute your own application details. If the examples do not
apply to your application, check the applicable parameter reference for the available options.
6.8.1

Level Application Example

SITRANS LUT400
Operating Instructions, 04/2021, A5E33329501-AG
Distance 8.5 m
1.0 m
Sensor reference point
High calibration point
Space 7.5 m
15.0 m
Level 6.5 m
Low calibration point
Far range
Commissioning
6.6 Device Address
79