TRACKSO INSTALLATION GUIDE FOR SECURE METER ELITE 103 -2,ELITE 303-2,ELITE 307-2
Brand:
Secure
Type:
METER
Models: ELITE 103-2, ELITE 303-2, ELITE 307-2
CONNECTION DIAGRAM
On the rear panel, Secure Elite Elite 103-2, ELite 303-2,Elite 307-2 has an RS-485 communication socket as shown in the following
figure.
1. Please unscrew the RS485 terminal as shown in Figure S1.
2. Connect the cables to the RS485 bus terminal blocks.
3. Please make the connections from Terminal Block chip to TrackSo IoT
Gateway as mentioned in the Table – ST1.
DEFAULT CONFIGURATION IN TRACKSO IOT GATEWAY
Inverter ID: 1 (Range: 1 to 247)
Baud Rate: 9600 (Default) (Values: 9600, 19200, 38400)
Data Bits: 8
Stop Bit: 1
Parity: N/A (None)
CONFIGURATION AT THE METER END
The Setup Mode can be used to configure the meter with the help of push buttons: The Setup Mode is password protected which
can be accessed only by users authorized to change the configurations
Password Entry
The following steps will guide you to access the Setup Menu:
Figure S1 – Rear view of Secure Elite 103-2,ELite 303-2,Elite 307-2
Secure Pin No. &
TrackSo Pin No. &
Assignment
1
A
3
2
B
4
3
SG
-
Table ST1 – Secure RS485 chip connections
with TrackSo IoT Gateway
Assignment
D+
D-
-