Download Print this page

Siemens Cerberus Pyrotronics PB-1191 Manual page 7

Linear smoke detection system

Advertisement

PB-1191 Beam Detector Manual
Detector
PBA-1191
• The effective region corresponds to the ribbon connecting transmitter, reflector and receiver.
• The core region contains sufficient radiation energy to operate the system.
• The energy in the scattered region is not sufficient to ensure reliable operation of the system.
Detector
PBA-1191
Alignment Possibilitites
The infrared beam can be adjusted by 10° increments horizontally and in 5° increments vertically from
the center axis. When selecting the optimum mounting location, remember that this adjustment range
can be fully used. Experience has shown that the detector and reflector should be arranged as parallel
as possible especially with distances of >162.5 feet, as this makes adjustment simpler.
Detector
PBA-1191
Horizontal adjustment range of the optical system - max. 10° each side of the axis
6
Effective
Core
region
region
Figure 5
Structure of the infrared beam
Figure 6
Diameter of the core region
Figure 7
Scattered
region
Reflector
PBR-1191
10°
10°
Reflector
PBR-1191
Reflector
PBR-1191
280 ft.
44 ft.
44 ft.
280 ft.

Advertisement

loading