Download Print this page
Siemens Sinteso Cerberus PRO Manual

Siemens Sinteso Cerberus PRO Manual

Asd aspirating smoke detector

Advertisement

Quick Links

Sinteso™ Cerberus™ PRO
ASD Aspirating smoke detector
FDA241, FDA221
A6V10331032_k_en_--
2021-06-28
Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET de-
tector line or for standalone operation
Patented technology
Early detection of a wider spectrum of particle sizes in the air
Configuration using the USB interface or the control panel via FDCC221S (op-
tional)
'ASD Asyst-Tool' software to assist with pipe configuration
Unique dust-resistant detection chamber
Intuitive front indicator for airflow and smoke value
Access to service functions
Different event protocols
Offline/online configuration supported
Cleaning function (FDA241)
4...20 mA output
Smart Infrastructure

Advertisement

loading

Summary of Contents for Siemens Sinteso Cerberus PRO

  • Page 1 Sinteso™ Cerberus™ PRO ASD Aspirating smoke detector FDA241, FDA221 Siemens aspirating smoke detector (ASD) for the addressed FDnet/C-NET de- tector line or for standalone operation ● Patented technology ● Early detection of a wider spectrum of particle sizes in the air ●...
  • Page 2 Properties ● Extended optical detection thanks to dual wavelengths (blue and infrared): The aspirat- ing smoke detectors FDA241 and FDA221 use dual-wavelength technology to trigger an alarm at the earliest possible moment. They are designed to protect small and medium- sized business-critical environments for monitoring areas of up to 800 m (FDA241) or 500 m...
  • Page 3 ● Mining industry ● Subway stations ● Agricultural operations ● All other applications with visible dust load Functions Indication The display contains clear, comprehensible bar graphs for smoke and airflow, as well as an alarm indicator, an error indicator, and a dust indicator (FDA241). When the housing cover is open, the operator has access to the 'Reset', 'Normalize Smoke', and 'Normalize Flow' functions, as well as the mini USB connector.
  • Page 4 High flow Blowing Fire 2 No smoke Normal flow Low flow Error Fire 1 Fault/test Pre-alarm Dust Opening the detector CAUTION Damage to the connection cable In order to prevent damage to the connection cable when positioning the housing cover, make sure that the connection cable has been routed correctly.
  • Page 5 Service LED indicators and buttons Flow OK As soon as the selftest for normal operation has been completed successfully, the 'Flow OK' LED starts to flash. Smoke OK As soon as the selftest for normal operation has been completed successfully, the 'Smoke OK' LED starts to flash.
  • Page 6 If the aspirating smoke detector is to be operated on the FDnet/C-NET, the communication interface FDCC221S (S24218-A201-A2) must be ordered separately. Accessories Communication interface FDCC221S ● For connecting the aspirating smoke detector to FDnet/C-NET ● Integrated 'line separator' function ● Additional MC link interface (port for 3.5 mm jack) ●...
  • Page 7 Battery FA2004-A1 (12 V, 12 Ah, VdS) ● For supplying fire control panels and aspirating smoke detectors with power ● Compatible with: – Fire control panels for the 'Sinteso' and 'Cerberus PRO' product lines – External power units for the aspirating smoke detectors FDA241 and FDA221 Battery FA2005-A1 (12 V, 17 Ah, VdS) ●...
  • Page 8 A6V10916591 Installation Aspirator (FDA241/FDA221) FDAZ291 Related documents such as environmental declarations, CE declarations, etc., can be down- loaded at the following Internet address: http://siemens.com/bt/download Notes Disposal The device is considered an electronic device for disposal in accordance with the European Guidelines and may not be disposed of as domestic garbage.
  • Page 9 Metric: 25 mm outer diameter (OD) Monitoring area (dependent on Up to 800 m² Up to 500 m² local provisions and standards) System compatibility Compatible with all Siemens FC20/FC720 (FS20/FS720 systems) Relay alarm outputs Can be selected with/without self- retention Nominal current 2.0 A at DC 30 V. Contact: NO/NC...
  • Page 10 FDA241 FDA221 Service area ● 'Status OK' LED ● ● Settings for reset functions ● Settings for smoke density and airflow Event log Non-volatile event memory with time and date stamp for: smoke density, airflow, detector status, and faults Event memory entries 20000 8000 Modification memory entries...
  • Page 11 Dimensional drawings FDA241, FDA221 FDAZ292 Smart Infrastructure A6V10331032_k_en_-- 2021-06-28...
  • Page 12 Issued by © Siemens Switzerland Ltd, 2013 Siemens Switzerland Ltd Technical specifications and availability subject to change without notice. Smart Infrastructure Global Headquarters Theilerstrasse 1a CH-6300 Zug +41 58 724 2424 www.siemens.com/buildingtechnologies Document ID A6V10331032_k_en_-- Edition 2021-06-28...

This manual is also suitable for:

Fda241Fda221Fdaz292Fdaz292-aa