Concealed pendent sprinklers quick & standard response, standard coverage

Advertisement

Quick Links

Series RFII — 5.6 K-factor
"Royal Flush II" Concealed Pendent Sprinklers
Quick & Standard Response, Standard Coverage
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/series-rfii-
5_6-k-royal-flush-quick-cov
General
Description
The TYCO Series RFII 5.6 K-factor,
"Royal Flush II" Concealed Pendent
Sprinklers Quick Response (3-mm
bulb) and Standard Response (5-mm
bulb), are decorative sprinklers fea-
turing a flat cover plate designed to
conceal the sprinkler. These sprinklers
are optimal for architecturally sensi-
tive areas such as hotel lobbies, office
buildings, churches, and restaurants.
Each sprinkler includes a Cover Plate/
Retainer Assembly and a Sprinkler/
Support Cup Assembly. The separa-
Page 1 of 4
ble, two-piece assembly design pro-
vides the following benefits:
• Allows installation of the sprinklers
and pressure testing of the fire pro-
tection system prior to installation of
a suspended ceiling or application of
the finish coating to a fixed ceiling.
• Permits the removal of suspended
ceiling panels for access to building
service equipment without having
to first shut down the fire protection
system and remove sprinklers.
• Provides for 1/2 in. (12,7 mm) of ver-
tical adjustment to allow a measure
of flexibility in determining the length
of fixed piping to cut for the sprinkler
drops.
The Series RFII Sprinklers are shipped
with a Disposable Protective Cap. The
Protective Cap is temporarily removed
during installation and replaced to help
protect the sprinkler during ceiling
installation or finish. The tip of the Pro-
tective Cap can be used to mark the
center of the ceiling hole into plaster
board or ceiling tiles by gently pushing
the ceiling product against the Pro-
tective Cap. When ceiling installa-
tion is complete, the Protective Cap is
removed and the Cover Plate/Retainer
Assembly is installed.
As an option, the Series RFII Standard
Response (5-mm bulb) "Royal Flush II"
Concealed Pendent Sprinklers can be
fitted with a silicone Air and Dust Seal.
See Figure 5. The Air and Dust Seal
is intended for sensitive areas where
it is desirable to prevent air and dust
from the area above the ceiling to pass
through the cover plate.
NOTICE
The Series RFII Concealed Pendent
Sprinklers described herein must be
installed and maintained in compliance
with this document and with the appli-
cable standards of the NATIONAL FIRE
PROTECTION ASSOCIATION (NFPA),
in addition to the standards of any
authorities having jurisdiction. Failure
to do so may impair the performance
of these devices.
The owner is responsible for maintain-
ing their fire protection system and
APRIL 2022
Worldwide
www.tyco-fire.com
Contacts
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Number (SIN)
TY3531 — 3 mm bulb
TY3551 — 5 mm bulb
Technical
Data
Sprinkler Approvals
Approvals apply only to the service
conditions indicated in the Design Criteria
section.
• TY3531 (3 mm Bulb) is UL Listed,
C-UL Listed and NYC Approved
(MEA 353-01-E) as Quick Response.
• TY3531 (3 mm Bulb) is EAC Approved
and VdS Approved (Certificate No.
G4090007).
• TY3531 (3 mm Bulb) is FM and
LPCB Approved (Ref. No. 094a/10) as
Standard Response.
Note: FM and LPCB do not approve
concealed sprinklers for quick
response.
• TY3551 (5 mm Bulb) is UL Listed, C-UL
Listed, EAC Approved, FM Approved,
LPCB Approved (Ref. No. 094a/9),
and NYC Approved (MEA 353-01-E) as
Standard Response.
TFP181

Advertisement

loading
Need help?

Need help?

Do you have a question about the Royal Flush II and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco Royal Flush II

  • Page 1 Worldwide www.tyco-fire.com Contacts Series RFII — 5.6 K-factor “Royal Flush II” Concealed Pendent Sprinklers Quick & Standard Response, Standard Coverage ble, two-piece assembly design pro- IMPORTANT vides the following benefits: Refer to Technical Data Sheet • Allows installation of the sprinklers...
  • Page 2 Ejection Spring ....Stainless Steel CEILING Design Criteria SOLDER COVER The TYCO Series RFII 5.6 K-factor, COVER PLATE/RETAINER TABS (3) PLATE “Royal Flush II” Concealed Pendent ASSEMBLY...
  • Page 3 TFP181 Page 3 of 4 FACE OF CLEARANCE HOLE CLEARANCE SPRINKLER DIAMETER HOLE FITTING DIMENSION C SPRINKLER SUPPORT CUP ASSEMBLY 1/2" (12,7 mm) THREADED ADJUSTMENT FACE OF CEILING, RETAINING RING FIGURE 4 MOUNTING SURFACE DISPOSABLE PROTECTIVE CAP Do not attempt to compensate for insufficient adjustment in the Sprinkler by under- or over-tightening the Sprin- kler/Support Cup Assembly.
  • Page 4 Seal is engaged. corrosion must be replaced. Specify: Series RFII (specify SIN), K=5.6, “Royal Flush II” Pendent Sprin- Step 8. Screw on the Cover Plate/ Automatic sprinklers must never be klers (specify) temperature rating, P/N*...