Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series RFII — 5.6 K-factor
"Royal Flush II" Concealed Pendent Sprinklers
Quick Response, Extended Coverage
General
Description
The Tyco
Series RFII, 5.6 K-factor,
®
Extended Coverage, Light Hazard
(ECLH) "Royal Flush" Concealed Pen-
dent Sprinklers are decorative, 3 mm
bulb-type sprinklers featuring a flat
cover plate designed to conceal the
sprinkler. These sprinklers are opti-
mal for architecturally sensitive areas
such as hotel lobbies, office buildings,
churches, and restaurants.
The Series RFII sprinklers are intended
for use in automatic sprinkler systems
designed in accordance with standard
13). The fast-response thermal sensi-
tivity rating of the Series RFII (TY3532)
provides for a quick response, extend-
ed coverage (QREC) rating up to a
20 ft. x 20 ft. coverage area.
Each sprinkler includes a Cover Plate/
Retainer Assembly and a Sprinkler/
Support Cup Assembly. The separable,
two-piece assembly design provides
the following benefits:
•
Allows installation of the sprinklers
and pressure testing of the fire pro-
tection system prior to installation
of a suspended ceiling or applica-
tion of the finish coating to a fixed
ceiling.
•
Permits the removal of suspended
ceiling panels for access to building
service equipment without having
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 4
to first shut down the fire protection
system and remove sprinklers.
•
Provides for 1/2 inch (12,7 mm) of
vertical adjustment to allow a mea-
sure of flexibility in determining the
length of fixed piping to cut for the
sprinkler drops.
The Series RFII Sprinklers are shipped
with a Disposable Protective Cap. The
Protective Cap is temporarily removed
during installation and replaced to help
protect the sprinkler during ceiling in-
stallation or finish. The tip of the Pro-
tective Cap can be used to mark the
center of the ceiling hole into plaster
board or ceiling tiles by gently push-
ing the ceiling product against the Pro-
tective Cap. When ceiling installation
is complete, the Protective Cap is re-
moved and the Cover Plate/Retainer
Assembly is installed.
NOTIce
The Series RFII Concealed Pendent
Sprinklers described herein must be
installed and maintained in compli-
ance with this document and with the
applicable standards of the National
Fire Protection Association, in addi-
tion to the standards of any authori-
ties having jurisdiction. Failure to do
so may impair the performance of
these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condi-
tion. The installing contractor or sprin-
kler manufacturer should be contact-
ed with any questions.
Sprinkler
Identification
Number (SIN)
TY3532
JULY 2009
Technical
Data
Approvals
UL and C-UL Listed
NYC Approved under MEA 353-01-E
(The listings apply only to the service
conditions indicated in the Design Cri-
teria section.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
K= 5.6 GPM/psi
1/2
(80,6 LPM/bar
Temperature Rating
155°F / 68°C Sprinkler with
139°F / 59°C Plate
200°F / 93°C Sprinkler with
165°F / 74°C Plate
Adjustment
1/2 inch (12,7 mm)
Finishes
See the Ordering Procedure section.
Physical Characteristics
Frame . . . . . . . . . . . . . . . . . . . Bronze
Support Cup. . . Chrome Plated Steel
Guide Pins . . . . . . . . . Stainless Steel
Deflector. . . . . . . . . . . . . . . . . Bronze
Compression Screw. . . . . . . . . Brass
Blub
. . . . . . . . . . . . . . . . . . . . . .Glass
Cap . . . . . . . . . . . . . Bronze or Copper
Sealing Assembly. . . . . . . . . . . . . . . .
. . . . . . . . . Beryllium Nickel w/ Teflon
Cover Plate . . . . . . . . . . . . . . . . Brass
Retainer . . . . . . . . . . . . . . . . . . Brass
Ejection Spring . . . . . . Stainless Steel
DuPont Registered Trademark
†