RAPID RESPONSE Series LFII Residential Sprinklers
4.2 K-factor Horizontal Sidewall
Wet Pipe and Dry Pipe Systems
General
Description
The TYCO RAPID RESPONSE Series
LFII Residential Horizontal Sidewall
Sprinklers (TY1334) are decorative,
fast response, frangible bulb sprinklers
designed for use in residential occu-
pancies such as homes, apartments,
dormitories, and hotels. When aesthet-
ics and optimized flow characteristics
are the major consideration, the Series
LFII Residential Sidewall Sprinklers
(TY1334) should be the first choice.
The Series LFII Residential Sprinklers
are intended for use in the following
scenarios:
• wet and dry pipe residential sprin-
kler systems for one- and two-fam-
ily dwellings and mobile homes per
NFPA 13D
• wet and dry pipe residential sprinkler
systems for residential occupancies
up to and including four stories in
height per NFPA 13R
• wet and dry pipe sprinkler systems
for the residential portions of any
occupancy per NFPA 13
The recessed version of the Series
LFII Residential Sprinklers is intended
for use in areas with finished walls.
It employs a two-piece Style 20
Recessed Escutcheon. The Recessed
Escutcheon provides 1/4 inch (6,4
mm) of recessed adjustment or up to
1/2 inch (12,7 mm) of total adjustment
from the flush mounting surface posi-
tion. The adjustment provided by the
Recessed Escutcheon reduces the
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 6
accuracy to which the pipe nipples to
the sprinklers must be cut.
The Series LFII Residential Sprinklers
have been designed with heat sensitiv-
ity and water distribution characteristics
proven to help in the control of residen-
tial fires and to improve the chance for
occupants to escape or be evacuated.
Dry Pipe System Application
The Series LFII Residential Horizon-
tal and Recessed Horizontal Sidewall
Sprinklers offers a laboratory approved
option for designing dry pipe residen-
tial sprinkler systems, whereas, most
residential sprinklers are laboratory
approved for wet systems only.
Through extensive testing, it has been
determined that the number of design
sprinklers (hydraulic design area) for
the Series LFII Residential Horizon-
tal Sidewall Sprinklers (TY1334) need
not be increased over the number of
design sprinklers (hydraulic design
area) as specified for wet pipe sprinkler
systems, as is accustomed for density/
area sprinkler systems designed per
NFPA 13.
Consequently, the Series LFII Resi-
dential Sprinklers offer the features of
non-water filled pipe in addition to not
having to increase the number of design
sprinklers (hydraulic design area) for
systems designed to NFPA 13, 13D, or
13R. Non-water filled pipe will permit
options for areas sensitive to freezing.
NOTICE
The Series LFII Residential Horizontal
Sidewall Sprinklers described herein
must be installed and maintained in
compliance with this document and
the applicable standards of the National
Fire Protection Association, in addi-
tion to the standards of any authori-
ties having jurisdiction. Failure to do so
may impair the performance of these
devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
JANUARY 2016
Worldwide
www.tyco-fire.com
Contacts
Sprinkler
Identification
Number (SIN)
TY1334
TFP410

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RAPID RESPONSE LFII Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco RAPID RESPONSE LFII Series

  • Page 1 Description The Series LFII Residential Sprinklers have been designed with heat sensitiv- The TYCO RAPID RESPONSE Series ity and water distribution characteristics LFII Residential Horizontal Sidewall proven to help in the control of residen- Sprinklers (TY1334) are decorative,...
  • Page 2: Technical Data

    TFP410 Page 2 of 6 Components: Frame WRENCH Button Assembly FLATS Sealing Assembly Bulb Compression Screw De ector TOP-OF- 7/16" (11,1 mm) 2-7/8" DIA. DEFLECTOR NOMINAL (73,0 mm) Temperature rating MAKE-IN is indicated on top of De ector. CENTERLINE OF WATERWAY 7/16"...
  • Page 3: Operation

    Residential Sprinkler Design within the TYCO Technical Data Sheet fitting. Guide TFP490 for the manufactur- TFP490. Step 3. Tighten the sprinkler into the er’s recommendations that may be...
  • Page 4: Care And Maintenance

    The TYCO RAPID RESPONSE Series operation in the event of a fire or inad- be replaced. Also, replace any sprin- LFII Residential Horizontal and vertent operation may result.
  • Page 5: Limited Warranty

    (specify*) finish, P/N (specify*) *Refer to Technical Data Sheet TFP770. For warranty terms and conditions, visit Contact your local distributor for Sprinkler Wrench www.tyco-fire.com. availability. When placing an order, Specify W-Type 6 Sprinkler Wrench, indicate the full product name and Part P/N 56-000-6-387 Number (P/N).
  • Page 6 TFP410 Page 6 of 8 GLOBAL HEADQUARTERS | 1400 Pennbrook Parkway, Lansdale, PA 19446 | Telephone +1-215-362-0700 Copyright © 2016 Tyco Fire Products, LP. All rights reserved. TEFLON is trademark of The DuPont Corporation...

This manual is also suitable for:

Ty1334Lfii series

Table of Contents