Summary of Contents for ABB 8408608

  • Page 1 — U S E R M A N UA L PowerValue 11 RT G2 6-10 kVA...
  • Page 2 A B B U P S P R O D U C T S A N D S O L U T I O N S — About this manual — Document information File name 04-3788_ABB_OPM_PVA11 6-10kVA-RT_G2_EN_REV-B UPS model PowerValue 11 RT G2 6-10 kVA Date of issue 06.04.2018 Issued by...
  • Page 3: Table Of Contents

    — Contents Important safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5 1 .1 Operator precautions .
  • Page 4 A B B U P S P R O D U C T S A N D S O L U T I O N S Communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30 5 .1 RS-232 port .
  • Page 5: Important Safety Instructions

    CABINET: DANGER OF ELECTRICAL SHOCK. accidental load loss. DANGER HIGH FAULT CURRENTS (LEAKAGE ABB DOES NOT TAKE ANY RESPONSIBILITY FOR CURRENTS). BEFORE CONNECTING THE MAINS ENSURE THAT THE UPS IS EARTHED! DAMAGES CAUSED THROUGH INCORRECT USE DANGER OF THE UPS SYSTEM .
  • Page 6: Declaration Of Safety Conformity And Ce Marking

    1 .4 Inquiries Inquiries regarding the UPS should be contacting ABB or authorized agent. The addressed to the local ABB office or agent serial number is shown on the nameplate authorized by ABB. Note the type code and of the product. For further information on the serial number of the equipment before troubleshooting, see Chapter 6.
  • Page 7: Maintenance

    (around three to five years at 25°C ambient temperature). Contact THE BATTERY CIRCUIT IS NOT ISOLATED FROM THE INPUT VOLTAGE. HAZARDOUS your local ABB or an agent authorized by ABB VOLTAGES MAY OCCUR BETWEEN THE for replacements. BATTERY TERMINALS AND THE GROUND.
  • Page 8 A B B U P S P R O D U C T S A N D S O L U T I O N S — 2 .1 UPS disposal and recycling 2 .1 .1 For professional users in the European Union 2 .1 .2 For disposal in countries outside of the European Union THE CROSSED –OUT WHEELED BIN...
  • Page 9: Installation

    3 I N S TA L L AT I O N — 3 Installation — 3 .1 Delivery, transportation, positioning and storage 3 .1 .1 Receipt of the UPS and visual inspection Rack-mounting accessories (full rack-mounting When receiving the UPS, carefully examine the kit can be purchased separately): packing container and the UPS for any signs of •...
  • Page 10: Site Planning And Positioning

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 3 .2 Site planning and positioning 3 .2 .1 Planning before the installation —...
  • Page 11: Standalone / Tower Installation

    3 I N S TA L L AT I O N 3 .2 .3 .2 External battery modules 3 .2 .4 Standalone / tower installation — 04 Battery module 3 .2 .4 .1 UPS Identify the final position and keep 3U spacing connection —...
  • Page 12 A B B U P S P R O D U C T S A N D S O L U T I O N S 3 .2 .4 .2 External battery modules — 7 Stabilizer bracket for 1. Set up the extension plate as below and install external batter module it on the UPS stabilizer bracket.
  • Page 13: General Characteristics

    3 I N S TA L L AT I O N — 3 .3 General characteristics 3 .3 .1 UPS front panel — 08 UPS front panel Figure 8 shows the front panel of the UPS. — 09 UPS rear view Normal Battery Bypass...
  • Page 14 A B B U P S P R O D U C T S A N D S O L U T I O N S — 10 External battery module rear view 11 15 — — Table 3: External battery module rear panel connectors and ports EBM terminal Fuse board cover (to replace EBM fuse)
  • Page 15: Electrical Installation

    BEFORE WORKING ON THIS CIRCUIT, and testing of the UPS, and customer training. CHECK FOR HAZARDOUS VOLTAGE. ABB recommends that an external isolating device is installed between the mains input DO NOT OPERATE IN CASE OF PRESENCE and UPS as shown in Figure 12 to protect OF WATER OR MOISTURE.
  • Page 16: Connections

    A B B U P S P R O D U C T S A N D S O L U T I O N S 3 .4 .3 Connections — 13 Terminal INDUCTIVE LOADS (FOR EXAMPLE block cover MONITORS AND LASER PRINTERS) HAVE —...
  • Page 17: Parallel Installation Operation

    3 I N S TA L L AT I O N 3 .4 .5 Parallel installation operation — 16 Parallel system Up to three UPSs can be connected in parallel to installation diagram configure a sharing and redundant output power. From Utility Mains Breaker I/P Breaker...
  • Page 18 A B B U P S P R O D U C T S A N D S O L U T I O N S How to install a new parallel UPS system: — 5. Connect the input and output wires and make 17 Parallel cable 1.
  • Page 19 3 I N S TA L L AT I O N 6. Turn on the input breakers for the parallel UPS. How to remove a single UPS from a parallel system: 7. Hold button for more than 1 s on one UPS in 1.
  • Page 20: Operation

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 4 Operation This chapter describes how the UPS is operated through the LCD. The user can: •...
  • Page 21: Lcd

    4 O P E R AT I O N 4 .1 .3 — Battery status Load/equipment status 21 The default LCD The LCD shows an overview of the status of the UPS: - Input Battery Load - Output - Battery - Load parameters - Working mode Output...
  • Page 22: Operating Mode

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 4 .2 Operating mode The following table describes the UPS status information: — Table 8: Symbols in operating mode Status Symbol...
  • Page 23: Ups Start-Up And Shutdown

    4 O P E R AT I O N — 4 .3 UPS start-up and shutdown 4 .3 .2 UPS shutdown SWITCH OFF THE CONNECTED LOADS To shut down the UPS with mains supply: BEFORE TURNING ON THE UPS. SWITCH 1.
  • Page 24: Display Functions

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 4 .4 Display functions Use the two middle buttons ( ) to When the UPS starts up, the display is in navigate the menu.
  • Page 25: User Settings

    4 O P E R AT I O N — 4 .5 User settings The following table displays the options that can be changed by the user. — Table 10: User settings Submenu Available settings Default settings Password Key the password USER Language [English][Deutsch][Español]...
  • Page 26: Lcd Operation

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 4 .6 LCD operation In addition to the default UPS status summary 4 .6 .2 UPS status menu —...
  • Page 27: Measurement Menu

    4 O P E R AT I O N 4 .6 .3 Measurement menu 4 .6 .4 Event log menu — 24 Measurement menu By pressing on the Measurement menu, By pressing on the Event log menu, — 25 Event log menu the next measurement menu tree is displayed.
  • Page 28: Control Menu

    A B B U P S P R O D U C T S A N D S O L U T I O N S 4 .6 .5 Control menu 4 .6 .6 Identification menu — 26 Control menu By pressing on the Control menu, By pressing...
  • Page 29: Setting Menu

    4 O P E R AT I O N 4 .6 .7 Setting menu — Example: set rated output voltage value. 28 Setting menu — 29 Example (set-up) PLEASE CONTACT YOUR LOCAL DISTRIBUTOR FOR FURTHER INFORMATION BEFORE CHANGING SETTINGS. SOME SETTINGS CHANGE THE SPECIFICATION OF THE UPS AND SOME SETTINGS ENABLE OR DISABLE SOME IMPORTANT FUNCTIONS.
  • Page 30: Communication

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 5 Communication A USB and an RS-232 port are available to enable If there is a power failure and a predicted the communication between the UPS and a shutdown of the UPS due to low battery remote computer/ station.
  • Page 31: Usb Port

    5 C O M M U N I C AT I O N — 5 .2 USB port The UPS can communicate with USB-compliant computers that run power management software. To establish communication between the UPS and a computer, connect the USB cable to the USB port on the UPS.
  • Page 32: Network Management Card (Optional)

    A B B U P S P R O D U C T S A N D S O L U T I O N S — 5 .4 Network management card (optional) The PowerValue 11 RT G2 6–10 kVA is equipped To install a network management card: with an intelligent slot for optional cards for 1.
  • Page 33: Troubleshooting

    6 T R O U B L E S H O OT I N G — 6 Troubleshooting — 6 .1 Fault identification and rectification Alarms and events indicate warnings and notify of errors or potential failures in the system. The output of the UPS is not necessarily affected when an alarm arises but taking the correct actions may prevent loss of power to the load.
  • Page 34 A B B U P S P R O D U C T S A N D S O L U T I O N S Alarm or Event Possible cause Remedy Battery mode The UPS is powering the equipment with Battery (Orange) LED is on.
  • Page 35 6 T R O U B L E S H O OT I N G Alarm or Event Possible cause Remedy BUS Under Voltage Fault (Red) LED is On. Indicates that the UPS has bus undervoltage The UPS transfers to bypass mode if Beep continuous.
  • Page 36: Silencing The Alarm

    A B B U P S P R O D U C T S A N D S O L U T I O N S Always have the following information available when calling the after-sales service department: 1. Model number and serial number 2.
  • Page 37 A P P E N D I X A — Appendix A CS141 SNMP card available parameters (valid for CS141 Basic, CS141 ModBus, CS141 Advanced) . The parameters available for CS141 SNMP cards are shown below. Parameter Units Type Available interface Modbus register Measurement Parameters Input Voltage...
  • Page 38 A B B U P S P R O D U C T S A N D S O L U T I O N S — Appendix B Winpower SNMP card available parameters (webserver interface) The parameters available from WinPower SNMP cards are shown below.
  • Page 39 A P P E N D I X B...
  • Page 40 — www.abb.com/ups ups.sales@ch.abb.com © Copyright 2018 ABB. All rights reserved. Specifications subject to change without notice.