Mitsubishi Electric FR-A802-P Instruction Manual page 16

Separated converter type for parallel operation
Table of Contents

Advertisement

• One circuit breaker and one magnetic contactor per converter unit
(When a single wound motor or a multi-wound motor is connected under V/F control or Advanced magnetic flux vector control )
Motor
Number of
output
units
(kW)

630
2
H400K
710
2
H450K
800
2
H500K
900
2
H560K
945
3
H400K
1065
3
H450K
1200
3
H500K
1350
3
H560K
(When a multi-wound motor is connected under Real sensorless vector control or Vector control)
Motor
Number of
output
units
(kW)

800
H400K
900
H450K
2
1000
H500K
1120
H560K

The motor output indicates the output power of a 4-pole motor at 400 VAC 50 Hz driven by all of the inverters in parallel connection.

Select an MCCB according to the power supply capacity.
(For the use in the United States or Canada, refer to

The magnetic contactor is selected based on the AC-1 class. The electrical durability of magnetic contactor is 500,000 times. When the
magnetic contactor is used for emergency stops during motor driving, the electrical durability is 25 times.
If using an MC for emergency stop during driving the motor, select an MC regarding the converter unit input side current as JEM 1038-AC-3
class rated current. When using an MC on the inverter output side for commercial-power supply operation switching using a general-purpose
motor, select an MC regarding the rated motor current as JEM 1038-AC-3 class rated current.
NOTE
• When the breaker on the converter unit's input side trips, check for the wiring fault (short circuit), damage to internal parts of
the inverter and the converter unit, etc. The cause of the trip must be identified and removed before turning ON the power of
the breaker.
Applicable
Molded case circuit breaker (MCCB)
converter unit
FR-CC2-[ ]-P
900 A
1000 A
1200 A
1500 A
900 A
1000 A
1200 A
1500 A
Applicable
Molded case circuit breaker (MCCB)
converter unit
FR-CC2-[ ]-P
900A
1000A
1200A
1500A
page 115
(NF type)
(NF type)
to select an appropriate fuse or molded case circuit breaker (MCCB).)
INSTALLATION AND WIRING
Peripheral devices
Input-side magnetic

contactor

S-N800
1000 A rated product
1000 A rated product
1200 A rated product
S-N800
1000 A rated product
1000 A rated product
1200 A rated product
Input-side magnetic

contactor

S-N800
1000 A rated product
1000 A rated product
1200 A rated product
2
15