Hitachi RED670 Commissioning Manual page 216

Hide thumbs Also See for RED670:
Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
1.
Connect the analog signals to the voltage inputs, in pair of two for U1 and U2. (Inputs U3PBB1,
U3PBB2, U3PLN1, U3PLN2)
2.
Activate the binary signals according to the used alternative. Verify the measuring voltage on
the synchronizing check function SESRSYN. Normally it can be good to verify synchronizing
check with the same voltages and phase angles on both voltages. The voltages should be
verified to be available when selected and not available when another input is activated so
connect only one voltage transformer reference at each time.
3.
Record the voltage selection tests in a matrix table showing read values and AUTOSYOK/
MANSYOK signals to document the test performed.
Testing the voltage selection for 1 1/2 CB arrangements
At test of the SESRSYN function for a 1½ CB diameter the following alternative voltage inputs can be
used for the three SESRSYN (SESRSYN 1, SESRSYN 2, SESRSYN 3) functions. These three
SESRSYN functions can either be in one, two or three different IEDs. Table
scenario when SESRSYN 1, SESRSYN 2 and SESRSYN 3 all are in the same IED. If SESRSYN 3 is
in another IED, WA1 will be considered as WA2 and LINE2 as LINE1. The voltage is selected by
activation of different inputs in the voltage selection logic as shown in table
Table 40:
SESRSYN
SESRSYN 1
(Operates on
WA1_QA1)
SESRSYN 2
(Operates on
TIE_QA1)
SESRSYN 3
(Operates on
WA2_QA1)
210
Voltage selection logic
CBConfig
Section to
setting
be
synchroniz
ed
1 ½ bus CB
WA1 –
LINE1
WA1 –
LINE2
WA1 –
WA2
Tie CB
LINE1 –
LINE2
WA1 –
LINE2
WA2 –
LINE1
WA1 –
WA2
1 ½ bus alt.
WA2 –
CB
LINE2
(mirrored)
WA2 –
LINE1
WA2 –
WA1
© 2017 - 2022 Hitachi Energy. All rights reserved
Activated
Activated
Activated
B1QCLD
B2QCLD
LN1QCLD
input on
input on
input on
IED from
IED from
IED from
TIE_QA1
TIE_QA1
WA2_QA1
WA1_QA1
WA2_QA1
WA1_QA1
WA2_QA1
TIE_QA1
TIE_QA1
WA1_QA1
1MRK 505 378-UEN Rev. K
GUID-12E7DA63-FE04-4C83-9BA6-34818C510DB8 v4
40
describes the
40
and figure 53.
Activated
Indication
LN2QCLD
from
input on
SESRSYN
IED from
on IED
LINE1_QB
B1SEL,
9
LN1SEL
LINE2_QB
B1SEL,
9
LN2SEL
B1SEL,
B2SEL
LINE1_QB
LINE2_QB
LN1SEL,
9
9
LN2SEL
LINE2_QB
B1SEL,
9
LN2SEL
LINE1_QB
B2SEL,
9
LN1SEL
B1SEL,
B2SEL
LINE2_QB
B2SEL,
9
LN2SEL
LINE1_QB
B2SEL,
9
LN1SEL
B1SEL,
B2SEL
Line differential protection RED670