Section 11
Testing functionality by secondary injection
11.4.12.3

Test of the boundary between zone 1 and zone 2, which is defined by the

parameter ReachZ1

The trajectory of the impedance traverses the lens characteristic in zone 2
Preliminary steady state test at 50 Hz
Go to Main menu /Test /Function status /Impedance protection /OutOfStep(78,Ucos) /
OOSPPAM(78,Ucos):1 /Outputs to check the available service values of the function block
OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is related to phase L1):
V
ts
EQUATION14065 V1 EN-US
V
EQUATION14058 V1 EN-US
frequency of V
I
50
s
EQUATION14059 V1 EN-US
∠I
50s
frequency of I
It
fs
EQUATION14062 V1 EN-US
∠I
tfs
frequency of I
Check that the service values (VOLTAGE, CURRENT, R(%), X(%)) are according to the injected
quantities and that ROTORANG is close to 3.14 rad. For this particular injection the service
values are:
Note that these values identify a point inside the lens characteristic, in the Zone 2, that is close to the
boundary between zone 1 and zone 2. The START is issued, but no TRIP is performed.
Execution of the dynamic test
The test may be performed by using two states of a sequence tool that is a basic feature of test sets.
State 1: pre-test condition.
Steady voltage and current are applied in order to get a steady high impedance, that is a point in
the plane R-X that is far away from the lens characteristic. Define the following three-phase
symmetrical quantities (the phase angle is related to phase L1):
142
V
,
VT s
1 1
.
1 1 1435
.
V
=
×
×
=
×
,
1
t RZ
V
VT p
,
ForwardX
=
 =
arctan
ts
ForwardR
= 50 Hz
ts
1
I
CTs
10459
I
=
×
=
×
50
9000
I
CTp
= 0º
= 50 Hz
50s
I
1
I
CTs
10459
=
×
=
×
tf
I
9000
CTp
= 0º
= 50 Hz
tfs
VOLTAGE = 1.58 kV
CURRENT = 20918 A
R = 1.08%
X = 7.85%
ROTORANG = -3.04 rad
© 2017 - 2022 Hitachi Energy. All rights reserved
0 1
.
11 44
.
V
×
=
13 8
.
59 33
.
 =
arctan
82. . 14°
8 19
.
= .
1 162
A
1 162
.
A
=
1MRK 505 378-UEN Rev. K
GUID-BE180E07-7D4B-4842-81FB-244DE8897430 v1
GUID-17F6AC8D-1F57-4245-A61D-776D469DD153 v1
GUID-3D42E43D-873E-4271-9AAF-3B2789FF3B17 v1
(Equation 40)
(Equation 41)
(Equation 42)
(Equation 43)
GUID-53964189-42E4-4C4B-BFCD-64888BA938EF v1
Line differential protection RED670
Commissioning manual