Tyco RFII-MRI Series Quick Start Manual

Tyco RFII-MRI Series Quick Start Manual

5.6 k-factor non-magnetic concealed pendent sprinklers quick & standard response, standard coverage

Advertisement

Series RFII-MRI — 5.6 K-factor
Non-Magnetic Concealed Pendent Sprinklers
Quick & Standard Response, Standard Coverage
IMPORTANT
Refer to Technical Data Sheet
TFP2300 for warnings pertaining to
regulatory and health information.
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and
installation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Scan the QR code or enter the URL
in a web browser to access the most
up-to-date electronic version of this
document. Data rates may apply.
docs.jci.com/tycofire/tfp182
General
Description
The TYCO Series RFII-MRI 5.6 K-fac-
tor, Non-Magnetic Concealed Pendent
Sprinklers Quick Response (3 mm bulb)
and Standard Response (5 mm bulb),
are decorative sprinklers featuring a
flat cover plate designed to conceal
the sprinkler.
Page 1 of 4
The RFII-MRI Sprinkler is intended for
use inside of a magnetic resonance
imaging (MRI) environment, that is, in
an MR system room and close to the
scanner unit. However, this sprinkler is
not intended for use directly inside of
the MR system, such as within the bore
of the scanner unit. During the intended
use, the RFII-MRI Sprinkler must be
mounted at the ceiling to the fixed fire
protection piping system of the MR
system room. Under these conditions,
per non-clinical testing to ASTM F2052-
15, the RFII-MRI Sprinkler was found
to be acceptable for use under a static
magnetic field of 7-Tesla or less. Stan-
dard MRI apparatus are typically in the
3 Tesla range.
Each sprinkler is comprised of the fol-
lowing separately ordered components:
• Cover plate/retainer assembly
• Sprinkler/support cup assembly
The separable, two-piece assembly
design provides the following benefits:
• Allows installation of the sprinklers
and pressure testing of the fire pro-
tection system prior to installation of
a suspended ceiling or application of
the finish coating to a fixed ceiling.
• Permits the removal of suspended
ceiling panels for access to building
service equipment without having
to first shut down the fire protection
system and remove sprinklers.
• Provides for 1/2 in. (12,7 mm) of ver-
tical adjustment to allow a measure
of flexibility in determining the length
of fixed piping to cut for the sprinkler
drops.
The RFII-MRI Sprinklers are shipped
with a disposable protective cap. The
protective cap is temporarily removed
during installation and replaced to help
protect the sprinkler during ceiling
installation or finish. The tip of the pro-
tective cap can be used to mark the
center of the ceiling hole into plaster
board or ceiling tiles by gently pushing
the ceiling product against the pro-
tective cap. When ceiling installa-
tion is complete, the protective cap is
removed and the cover plate/retainer
assembly is installed.
AUGUST 2022
Worldwide
www.tyco-fire.com
Contacts
As an option, the RFII-MRI Standard
Response (5 mm bulb) Sprinkler can
be fitted with a silicone air and dust
seal as shown in Figure 5. The air and
dust seal is intended for sensitive areas
where it is desirable to prevent air and
dust from the area above the ceiling to
pass through the cover plate.
NOTICE
The RFII-MRI Sprinklers described
herein must be installed and main-
tained in compliance with this docu-
ment and with the applicable standards
of the NATIONAL FIRE PROTECTION
ASSOCIATION (NFPA), in addition to
the standards of any authorities having
jurisdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for maintain-
ing their fire protection system and
devices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted with
any questions.
Sprinkler
Identification
Number (SIN)
TY3530 — 3 mm bulb
TY3550 — 5 mm bulb
TFP182

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the RFII-MRI Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco RFII-MRI Series

  • Page 1 Description drops. manufacturer should be contacted with any questions. The RFII-MRI Sprinklers are shipped The TYCO Series RFII-MRI 5.6 K-fac- Sprinkler with a disposable protective cap. The tor, Non-Magnetic Concealed Pendent protective cap is temporarily removed Sprinklers Quick Response (3 mm bulb)
  • Page 2: Operation

    TFP182 Page 2 of 4 Technical 1/2" NPT SEALING ASSEMBLY Data Sprinkler Approvals FRAME TY3530 (3 mm bulb) • UL Listed, C-UL listed as quick response • FM approved as standard response SUPPORT CUP WITH BULB TY3550 (5 mm bulb) ROLL FORMED •...
  • Page 3 TFP182 Page 3 of 4 by under- or over-tightening the sprin- FACE OF CLEARANCE HOLE kler/support cup assembly. Re-adjust SPRINKLER DIAMETER the position of the sprinkler fitting to FITTING DIMENSION C suit. Step 1. Install the sprinkler only in the SPRINKLER pendent position with the center-line SUPPORT CUP...
  • Page 4: Care And Maintenance

    The Series RFII-MRI Concealed For warranty terms and conditions, visit by wiping the sprinkler with a cloth or Pendent Sprinklers must be maintained www.tyco-fire.com. by brushing it with a soft bristle brush. and serviced in accordance with this Ordering section.
  • Page 5: Issue Date

    Worldwide www.tyco-fire.com Contacts TFP182 Change History Appendix ISSUE DATE NOTES Page 1, added QR code and URL to allow convenient access to electronic version from printed docu- ment; Page 4, changed corporate address and telephone number to 1467 Elmwood Avenue, Cranston,...

This manual is also suitable for:

Ty3530Ty3550

Table of Contents