Page 2
State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65warnings.ca.gov Kohler strongly recommends that only factory- authorized dealers install and service the generator. Product Identification Information Product identification numbers determine service parts.
Safety Precautions and Instructions IMPORTANT SAFETY INSTRUCTIONS. Electromechanical equipment, including generator sets, transfer switches, switchgear, and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. To prevent accidents be aware of potential dangers and act safely. Read and follow all safety precautions and instructions. SAVE THESE INSTRUCTIONS.
Page 6
Battery WARNING Sulfuric acid in batteries. Can cause severe injury or death. Wear protective goggles and clothing. Battery acid may cause blindness and burn skin. WARNING Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks. Locate the battery in a well‐ventilated area.
Page 7
Engine Backfire/Flash Fire WARNING Risk of fire. Can cause severe injury or death. Do not smoke or permit flames or sparks near fuels or the fuel system. Servicing the air cleaner. A sudden backfire can cause severe injury or death. Do not operate the generator set with the air cleaner removed.
Page 8
Fuel System WARNING Explosive fuel vapors. Can cause severe injury or death. Use extreme care when handling, storing, and using fuels. The fuel system. Explosive fuel vapors can cause severe injury or death. Vaporized fuels are highly explosive. Use extreme care when handling and storing fuels.
Page 9
Hazardous Voltage/Moving Parts DANGER Hazardous voltage. Will cause severe injury or death. This equipment must be installed and serviced by qualified electrical personnel. DANGER Hazardous voltage. Moving parts. Will cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. WARNING Hazardous voltage.
Page 10
Heavy Equipment WARNING Unbalanced weight. Improper lifting can cause severe injury or death and equipment damage. Do not use lifting eyes. Lift the generator set using lifting bars inserted through the lifting holes on the skid. Hot Parts WARNING Hot engine and exhaust system. Can cause severe injury or death.
Do not install or operate this generator set indoors. Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and the products represented without notice and without any obligation or liability whatsoever.
Page 12
Generator Set Literature Literature Part No. Specification Sheet, 14RCA/L G4-270 Specification Sheet, 20RCA/L G4-272 Specification Sheet, 26RCA/L G4-315 Installation Manual, Generator Set TP-7091 Operation Manual, Generator Sets TP-7092 Warranty Registration and Controller Unlock Code...
• Visit the Kohler Co. website at KOHLERPower.com. • Look at the labels and decals on your Kohler product or review the appropriate literature or documents included with the product. • Call toll free in the US and Canada 1-800-544-2444.
Have the generator set installed by an authorized Kohler dealer or authorized representative. For all locations, ensure that the installation complies with applicable national and local codes. In the United States, the installation must comply with the National Electrical Code (NEC) and local codes.
Model Weight, kg (lb.)* 14RCA 200 (440) 20RCA 252 (555) 26RCA 283 (625) Weights include generator set and packaging with skid; no battery or ATS. Figure 3 Approximate Weights Raise the roof and lift the air intake side and exhaust end panels up and off.
1.3 Generator Set Inspection Complete a thorough inspection of the generator set. Check for the following: Inspect the generator set for loose or damaged parts or wires. Repair or tighten any loose parts before installation. Check the engine oil. Fill, if necessary, with the recommended viscosity and grade of oil. Use synthetic oil, API (American Petroleum Institute) Service Class SG or higher.
1.4.2 Exhaust Requirements Figure 5 gives the exhaust temperature at rated load. The engine exhaust mixes with the generator set cooling air at the exhaust end of the enclosure. Mount the generator set so that the hot exhaust does not blow on plants or other combustible materials. Maintain the clearances shown in the dimension drawing.
1.6 Access the Air Intake Area The battery, fuel system, and some electrical connections are located in the air intake area. Remove the enclosure panel to access the air intake area during installation as described below. No tools are required to remove and replace the service-side, air intake end, or exhaust end panels.
2.1.3 Connecting the Fuel Supply The dimension drawing in the Drawings and Diagrams section shows the location of the fuel inlet connection. Have the fuel supplier install rigid gas piping and a manual fuel shut-off valve. The fuel supply line should line up with the generator set fuel inlet and end about 12 inches away to allow connection with a section of flexible fuel line.
2.2.1 Fuel Conversion, Original Fuel System, 14RCA/L For natural gas and LPG fuel, orifice fittings are used in the fuel line. See Figure 12. The natural gas orifice fitting is silver in color and stamped NG. The LPG fitting is gold in color and stamped LPG. The fittings are threaded. A straight-blade screwdriver is required to remove and replace the fittings.
Page 26
Procedure to Convert from NG to LPG, 14RCA/L Press the OFF button on the generator set controller. Disconnect the utility power to the generator. Disconnect the generator set engine starting battery, negative (-) lead first. Turn off and disconnect the fuel supply. Remove the hose clamp and fuel hose from the hose fitting.
2.2.2 Fuel Conversion, Original Fuel System, 20RCA/L For LPG fuel, an orifice is used in the fuel line. The unit is typically shipped set up for natural gas, with the loose orifice tied near the fuel solenoid valve. To convert to LPG, install the LPG orifice as described below. See Figure 15 for the fuel system component locations.
2.2.3 Fuel Conversion, Revised Fuel System, 14/20/26RCA/L The revised fuel system uses a knob that controls a valve on the regulator to select the fuel type. See Figure 16 and Figure 17. Fuel selector Fuel inlet Integral fuel solenoid valve...
Page 29
Fuel Selection, Revised Fuel System Press the OFF button on the generator set controller. Disconnect utility power to the generator set (open the corresponding circuit breaker in the distribution panel). Disconnect the generator set engine starting battery, negative (-) lead first. Turn off the fuel supply.
Page 30
Find the ignition timing leads 65 and N, located near the regulator. See Figure 20. For natural gas (NG), connect lead 65 to lead N3. For LPG, disconnect lead 65 from lead N3. Ignition timing leads Figure 20 Ignition Timing Leads Connect and turn on the fuel supply (Ensure that the fuel supply matches the fuel setting).
Section 3. Electrical 3.1 Electrical Connections DANGER Hazardous voltage. Will cause severe injury or death. This equipment must be installed and serviced by qualified electrical personnel. Grounding electrical equipment. Hazardous voltage will cause severe injury or death. Electrocution is possible whenever electricity is present.
3.1.2 Grounding Ground the generator set. The grounding method must comply with NEC and local codes. Connect the ground to the generator set ground lug, terminal GND in the customer connection area. See Figure 22. The requirement for having a bonded (grounded) neutral or ungrounded neutral is determined by the type of installation. The generator is shipped with a floating Neutral.
3.1.3 Electrical Lead Entry Drill or punch holes in the enclosure for the electrical conduit in the locations shown in Figure 23. To avoid interference with the roof when it is open, use a 90-degree elbow at the AC voltage entry point and direct the conduit away from the roof. DO NOT DRILL HOLES IN THESE AREAS ADV- 9746...
3.1.4 Field Connections Customer connection points are located as shown in Figure 24. Open the enclosure roof and locate the cover panel over the circuit breaker. Remove the cover panel to access the power and load connections. Remove the air intake end panel for access to the engine start and communication connections to the transfer switch. See the ATS and Accessory Communication Connections section for more details about the transfer switch connections.
Page 35
4 (See detail) LOW VOLTAGE CONNECTION DETAIL GM101741C GM101739 Cover panel. Remove for access to power and load connections. Cover panel screws, qty. 2. Load circuit breaker. Transfer switch and accessory low voltage connections. Use cable tie to secure low voltage connections. Ground connection for communication cable shield.
3.2 Battery WARNING Sulfuric acid in batteries. Can cause severe injury or death. Wear protective goggles and clothing. Battery acid may cause blindness and burn skin. WARNING Explosion. Can cause severe injury or death. Relays in the battery charger cause arcs or sparks. Locate the battery in a well‐ventilated area.
Page 38
Battery Description Starting batteries are usually the lead-acid type. Use a 12-volt group 51 battery with a minimum rating of 500 cold cranking amps at 0°F. The generator set uses a negative ground with a 12-volt engine electrical system. See Figure 26 for battery connections. Make sure that the battery is correctly connected and the terminals are tight.
3.3 ATS and Accessory Communication Connections The following sections cover communication connections from the generator set to automatic transfer switches and RBUS accessories, including the programmable interface module (PIM) and the load shed kit. 3.3.1 Communication Cable Specifications RBUS Connections A and B For the RBUS communication connections A and B to the optional RBUS modules, use 20 AWG shielded, twisted-pair communication cable.
3.3.2 Transfer Switch Connection Connect the ATS or remote start/stop switch. Connect the load leads from the generator set to the Emergency source lugs on the ATS. Route low-voltage communication leads through separate conduit from the AC power and load leads. All connections must comply with applicable state and local codes.
Generator Set (with engine start contacts) tp6803 Generator Set Terminal Block. Check the decal on the generator set for terminal block connections. Engine start leads 3 and 4. See the ATS manual for cable size specifications. Figure 29 Engine Start Connections with Transfer Switch Models other than Model RXT 3.3.3 System Connections with Accessory Modules See Figure 30 through Figure 34 for connection options to RBUS accessory modules.
Page 42
Generator Set 12 VDC Load Shed Kit RBUS Note: Connect A to A, B to B, PWR to PWR, and COM to COM. See the Communication Cable Specifications section. RXT transfer switch with standard or combined interface/ load management board. Do not use a load shed kit with RXT* a combined interface board.
Page 43
Generator Set 12 VDC RBUS Load Shed Kit B PWR COM Note: See the Communication Cable Specifications section for maximum total cable lengths. RXT* RXT transfer switch with standard or combined interface/ load management board. Do not use a load shed kit with a combined interface board.
Page 44
Generator Set RXT ATS Terminal Block Load Shed Kit Notes: • Check the decal on the generator set for terminal block connections. • 3 runs with 1 module each shown. • See Figure 30 for communication connection detail (A and B, PWR and COM).
Section 4. Prestart 4.1 Prestart Installation Check DANGER Hazardous voltage. Moving parts. Will cause severe injury or death. Operate the generator set only when all guards and electrical enclosures are in place. WARNING Carbon monoxide. Can cause severe nausea, fainting, or death. The exhaust system must be leakproof and routinely inspected.
4.2.2 Loaded Exercise ® In order to set a loaded exercise using the RDC2 controller, a Kohler Model RXT transfer switch must be connected. See the generator set operation manual for instructions to set a loaded exercise. To set a loaded exercise on a generator set connected to a transfer switch other than a Model RXT, use the transfer switch controller to set the exercise.
Section 5. Accessories 5.1 Introduction This section describes some of the accessories that are available for the generator sets. Have accessories installed by an authorized dealer or a licensed electrician. This document does not contain installation instructions for accessories. Follow the installation instructions provided with each kit.
Page 48
Heater Thermostat Power plug GM19463 Carburetor Heater for 14 kW Models Power plug Thermostat Heater Carburetor Heater for 20 and 26 kW Models GM57968 240 Volt Plug Figure 37 Carburetor Heaters Carburetor heater power cord Carburetor heater (air cleaner removed to show heater) tp6195 Figure 38...
Page 49
adv-8954 tt1482b Carburetor heater location under air cleaner. Insert Carburetor heater from the back of the generator set. 20 kW Model Carburetor heater 26 kW Model Figure 39 Carburetor Heater Location on 20 and 26 kW Models 120 VAC receptacle location Knockouts for 240 VAC plugs Figure 40 Power Connections for Carburetor Heaters...
Plus program. If an output is activated or deactivated through OnCue Plus, it is no longer controlled by the RDC2 controller. Kohler SiteTech software can be used to set the outputs back to generator-controlled events, if necessary. See the OnCue Plus manuals for instructions.
5.4 OnCue Plus Generator Management System ® The OnCue Plus Generator Management System allows monitoring and control of your generator set from a personal computer, smart phone, or tablet. OnCue Plus can also be configured to send email or text message notifications in the event of a generator set fault.
Up to four normally closed power relays can be connected through normally open relay contacts on the circuit board. ® See the load shed kit installation instructions for relay specifications. Kohler Power Relay Modules are recommended. Two relays are included on the load management device to control two independent heating, ventilation, and air conditioning (HVAC) loads.
5.5.1 Power Relay Module The power relay module kit contains one 50 amp normally closed relay with connecting lugs in a NEMA type 3R enclosure. Connect up to four (4) power relay modules to the load management devices listed above. The power relay modules can be mounted indoors or outdoors.
Page 54
Two single-phase generator sets as described above. APM RDC2.4 paralleling firmware for the blue-board controller on each generator set. Download the latest version of paralleling firmware from the Service Support section of the Kohler Power Resource Center (KPRC). One Model RXT automatic transfer switch (ATS).
5.7 Cold Weather Package The cold weather package is recommended for reliable operation at temperatures below 0°C (32°F). The cold weather package includes the kits shown in the following sections. The kits shown below are also available separately. WARNING Hot engine and exhaust system. Can cause severe injury or death.
Battery Heater Connection (26 RCA/L Models) Connect one end of the battery heater cable to the wire harness at P21. See the Drawings and Diagrams section for the connection details. Connect battery heater cable to wire harness GM119028 Figure 49 Battery Heater Connection, 26 RCA/L 5.7.2 Breather Tube and Oil Heater...
Page 57
120 VAC female connector Heating element (connect to oil heater) Label 120 VAC plug Thermostat 14 and 20 kW Models Heating element female connector (connect to oil heater) Label Thermostat Pin Connector 26 kW Models GM110893-CMP Figure 52 Breather Tube Heater Label Heating element Heating probe...
Fuel Regulator Heater (20 and 26 kW models only) An optional fuel regulator heater is recommended for models 20RCA/L and 26RCA/L for improved cold starting in locations where the ambient temperature drops below -18°C (0°F). The heater requires a continuous source of AC power.
Page 59
Place spacer between regulator and mounting bracket GM79141 Figure 57 Fuel Regulator Heater Installation, 20RCA/L and 26RCA/L Fuel Regulator Heater Connection (26 RCA/L Models) Disconnect the receptacle harness from connector P20. See Figure 58. Connect one end of the regulator heater cable to P20 and the other end to the receptacle harness.
The alternator weather cover is used to prevent frost and snow build up on the alternator brushes. The alternator weather cover is not applicable to the 26RCA/L generator set. Follow the instructions provided with the kit to install the alternator weather cover onto the alternator end bracket.
Appendix A. Abbreviations A, amp ampere blk. htr. block heater digital to analog converter ABDC after bottom dead center BMEP brake mean effective pressure decibel alternating current bits per second dB(A) decibel (A weighted) analog to digital Brass direct current advanced digital control;...
Page 88
(2 bytes) megabyte (2 bytes) gallons per hour KBus Kohler communication protocol MCCB molded-case circuit breaker gallons per minute kilogram one thousand circular mils grade, gross kg/cm kilograms per square meggar megohmmeter centimeter...
Page 89
N, norm. normal (power source) permanent magnet generator silicon controlled rectifier (electrical), selective catalytic reduction (exhaust emissions) not available, not applicable potentiometer, potential s, sec. second Systeme international d’unites, nat. gas natural gas parts per million International System of Units National Bureau of Standards PROM programmable read-only...
Page 90
ultrahigh frequency user interface Underwriter’s Laboratories, Inc. unified coarse thread (was NC) unified fine thread (was NF) univ. universal uniform resource locator (web address) undersize, underspeed ultraviolet, undervoltage volt volts alternating current voltampere reactive volts direct current vacuum fluorescent display video graphics adapter very high frequency watt...
Need help?
Do you have a question about the 26RCA and is the answer not in the manual?
Questions and answers
Can l have this Kohler 26RCA Installation Manual in french
Is there a required distance from the secondary( low pressure ) LP gas regulator to the generator fuel inlet?
What is the purpose of the 3/4" rubber hose in the Air intake section. It leads from the electrical housing at the top of the enclosure about 10" straight down terminating in a brass. Is it a drain of some sort? What to do with it?
What size concrete pad is recommend
A 4-inch concrete mounting pad is recommended for Kohler part number 26RCA.
This answer is automatically generated