Paperless recorder terminal block failures
Hide thumbs Also See for ScreenMaster RVG200:

Advertisement

3. Insert a flat-bladed screwdriver into each slot
slots) to release the locking arm and pull terminal block D
away from the case.
4. Check the position of spring contacts E within the
terminal block assembly.
The correct position for the contacts is as shown in Fig. 4.1
– each contact must be positioned a minimum of halfway
across the slot in which the module board fits.
5. If a contact is positioned incorrectly or is damaged, replace
the terminal block assembly.
6. Fit the terminal block.
7. Refit terminal cover B.
Fig. 4.1 Examining the terminal block contacts
C
in turn (2
A
B
E
Contact us
ABB Limited
Process Automation
Howard Road
St. Neots
Cambridgeshire PE19 8EU
UK
Tel:
+44 (0)1480 475321
Fax:
+44 (0)1480 217948
ABB Inc.
Process Automation
C
125 E. County Line Road
Warminster
PA 18974
USA
Tel:
+1 215 674 6000
Fax:
+1 215 674 7183
www.abb.com
Note
We reserve the right to make technical changes or modify the contents of this
document without prior notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB does not accept any responsibility whatsoever for
potential errors or possible lack of information in this document.
We reserve all rights in this document and in the subject matter and illustrations
contained therein. Any reproduction, disclosure to third parties or utilization of its
contents in whole or in parts – is forbidden without prior written consent of ABB.
D
Copyright© 2015 ABB
All rights reserved

Advertisement

loading