Table 5.18 9910/9960 Component Power And Heat Output Specifications; Table 5.19 9900 Subsystem Power And Heat Output Specifications - Hitachi 9900 User And Reference Manual

A subsystem
Hide thumbs Also See for 9900:
Table of Contents

Advertisement

Table 5.18
9910/9960 Component Power and Heat Output Specifications
Subsystem
9960
9910/9960
Table 5.19
9900 Subsystem Power and Heat Output Specifications
Subsystem
Type
Subsystem Configuration
9960
Controller with 32 GB cache, 4 sets of 8-port Adapters and 1 fully populated
Disk Array frame using 47-GB / 73-GB drives
Controller with 32 GB cache, 4 sets of 8-port Adapters and 2 fully populated
Disk Array frames using 47-GB / 73-GB drives
Controller with 32 GB cache, 4 sets of 8-port Adapters and 3 fully populated
Disk Array frames using 47-GB / 73-GB drives
Controller with 32 GB cache, 4 sets of 8-port Adapters and 4 fully populated
Disk Array frames using 47-GB / 73-GB drives
Controller with 32 GB cache, 4 sets of 8-port Adapters and 5 fully populated
Disk Array frames using 47-GB / 73-GB drives
Controller with 32 GB cache, 4 sets of 8-port Adapters
and 6 fully populated Disk Array frames using 47-GB / 73-GB drives
9910
16 GB cache, 3 sets of 8-port adapters, fully populated with 18-GB drives
16 GB cache, 3 sets of 8-port adapters, fully populated with 47- or 73-GB drives
112
Chapter 5 Planning for Installation and Operation
Component
Basic Controller frame with:
- first ACP pair (2 cards total)
- no cache or shared memory (2 empty cache cards)
Controller frame with:
- two ACP pairs (4 cards total)
- 4-GB cache, shared memory
- one 8-Port ExSA™ or Fibre adapter (2 cards total)
Controller frame with all options:
- four ACP pairs (8 cards total)
- 32-GB cache and associated shared memory (4 cards total)
- four 8-Port Serial/Fibre adapters (8 cards total)
- additional power supplies for >2 channel/fibre adapters
Empty array frame
Disk Array frame with maximum amount of 18-GB hard drives
Disk Array frame with maximum amount of 47-GB or 73-GB hard drives
Disk Array frame with maximum amount of 180-GB hard drives
Each array group:
RAID-5/RAID-1, 18-GB disk drives (Qty 4)
RAID-5/RAID-1, 47-GB, 73-GB, or 146-GB disk drives (Qty 4)
RAID-5/RAID-1, 180-GB disk drives (Qty 4)
Spare disk drives:
18-GB
47-GB, 73-GB, or 146-GB
180-GB
Power
Heat
(kVA)
(kW)
0.95
0.89
1.3
1.2
2.41
2.32
0.704
0.561
3.14
2.85
3.72
3.43
3.04
2.754
0.072
0.072
0.096
0.096
0.068
0.068
0.018
0.018
0.024
0.024
0.017
0.017
Power
Heat
(kVA)
(kW)
6.13
5.75
9.85
9.18
13.57
12.61
17.29
16.04
21.01
19.47
24.73
22.9
3.06
2.81
3.34
3.10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Freedom storage lightning 9900

Table of Contents