SIMO_CHN Function
4.4 Description of Parameters
Bit
0.6
0.7
1.0
:
1.7
2.0 - 3.7 I23
Refer INBT2 assignment. (Page 56)
4.4.4

SIMO_STAT Status Display

SIMO_STAT is used to actuate the status display:
• Low Byte: identifier for the respective device state (see: Actuation of Status Display)
•   High Byte: identifier for SIMOCODE Function
– 16#00: OVL
– 16#08: SOFT
– 16#10: DIR
– 16#20: REV
– 16#30: STAR
– 16#40: DAHL
– 16#50: POL
– 16#60: VALVE
– 16#70: POS
4.4.5

VSTATUS and VSTATUS1 Status Display

The most important statuses and enable signals are passed through VSTATUS and VSTATUS1.
VSTATUS Bit_31:=QCSF;
VSTATUS Bit_30:=QOFF;
VSTATUS Bit_29:=QON2;
VSTATUS Bit_28:=QON1;
VSTATUS Bit_27:=QCUR;
VSTATUS Bit_26:=QG_FLT;
VSTATUS Bit_25:=QG_WRN;
VSTATUS Bit_24:=Q1_2;
VSTATUS Bit_23:=Q1_3;
58
Meaning
SIMORESET; L_SIMORESET Standard function blocks - Reset1 -> [062] DP Bit 0.6 Receive
Always output by the block
as TRUE
I1_0
:
I1_7
Programming and Operating Manual, 11/2022, A5E51265657002A/RS-AC/003
Configuration in PDM / WinSIMOCODE-DP
Fault response -> PLC-CPU Signal -> [063] DP Bit 0.7 Receive
user-specific assignment
user-specific assignment
VSTATUS Bit_15:=LOCK;
VSTATUS Bit_14:=LOCK_ON;
VSTATUS Bit_13:=LOCK_OPT;
VSTATUS Bit_12:=VL_OPEN;
VSTATUS Bit_11:=VL_CLOSE;
VSTATUS Bit_10:=VL_HOLD;
VSTATUS Bit_09:=SS_POS;
VSTATUS Bit_08:=QCTA;
VSTATUS Bit_07:=QLTA;
SIMOCODE DP PCS 7 Library Migration (Legacy) - V9.1 SP2