If the Modbus-TCP/SNMP protocol is used, customers can purchase the NetEco (a LAN switch is
required) or a third-party NMS as the monitoring system.
CAN Teamwork + RS485 Monitoring
Networking Teamwork
Protocol
CAN
One teamwork network
supports a maximum of
32 units. On the
Teamwork Settings
Description
screen of the display
modules of the first and
last units, set Enable
teamwork CAN resistor
to Yes.
Connect the
COM/FE port
on the main
control module
of the last unit
in each group
to the RS485
port on the
host.
Customers can
purchase the
NetEco (an
ECC is
required) or a
third-party
NMS as the
monitoring
system.
Monitoring
Modbus-TCP
It takes 3 x n seconds to collect data from n units. If the
time required for the host to collect data from all units
does not meet the performance requirements, group the
units.
If units are not grouped (n = 1), set RS485
monitoring grouping to Enable on the Modbus
Settings screen for each unit.
If units are grouped (n > 1; recommended: n ≤ 4), set
RS485 monitoring grouping to Enable on the
Modbus Settings screen for the unit with the COM/FE
port connected. Retain the default setting (Disable)
for other units.