Table 1.5 Detail Of Specifications - Mitsubishi Electric 2033G Series Owner Technical Manual

Table of Contents

Advertisement

MITSUBISHI
ELECTRIC

TABLE 1.5 Detail of Specifications

Rated Output kVA
Rated Output kW
Configuration
Voltage
Frequency
Reflected Current THD
Type
Nominal Voltage
Minimum Voltage
Number of Cells
Configuration
Voltage
Voltage Stability
Frequency
Frequency Stability
Power Factor
Power Factor range
Voltage THD
Transient Response
Transient Recovery
Voltage Unbalance
Phase Displacement
Inverter Overload
Bypass Overload
Crest Factor Capabilities
Cooling
Operating Temperature
Relative Humidity
Altitude
Location
Paint Color
2033G SERIES UPS
OWNERS / TECHNICAL MANUAL
30
24
AC INPUT CHARACTERISTICS
3 phase, 4 wire
120/208 V
+15% ~ -25%
60 Hz +/- 5%
4% typ. at 100% load; 7% typ. at 50% load
BATTERY
VRLA
432 Vdc
367 Vdc
216
AC OUTPUT
3 phase, 4 wire
120/208 V
+/-2%
60 Hz
+/-0.01% in free running mode
0.8 nominal
0.8 ~ 1.0 lagging (within output kW rating)
2% typical THD at 100% Linear Load
5% typical THD at 100% non-linear load
+/-5% typical at 100% load step
+/-2% typical at loss/return of AC power
+/-5% typical at load transfer to/from static bypass
16.7 ms
3% typical at 100% unbalanced load
1deg. typical at 100% load
150% for 1 minute
150% for 1 minute, 1000% for 1 cycle
3:1
ENVIRONMENTAL
Forced Air
32゚F ~ 104゚F (0゚C ~ 40゚C).
Recommended 59゚F ~ 77゚F (15゚C ~ 25゚C)
5% ~ 95% Non Condensing
0 ~ 7400 feet No De-rating
Temperature-controlled, indoor area free of conductive contaminants
Munsell 5Y7/1 (Beige)
MITSUBISHI ELECTRIC 2033G SERIES UPS
Page Number:
1-13
50