Table 1.3 Detail Of Specifications - Mitsubishi Electric 2033D SERIES Owner Technical Manual

Mitsubishi power supply owner's manual
Table of Contents

Advertisement

MITSUBISHI
ELECTRIC

TABLE 1.3 Detail of Specifications

Rated Output kVA
Rated Output kW
Configuration
Voltage
Frequency
Reflected Current THD
Configuration
Voltage
Frequency
Type
Ride Through
Nominal Voltage
Minimum Voltage
Number of Cells
Configuration
Voltage
Voltage Stability
Frequency
Frequency Stability
Power Factor
Power Factor range
Voltage THD
Transient Response
Transient Recovery
Inverter Overload
System Overload
Bypass Overload
Cooling
Operating Temperature
Relative Humidity
Altitude
Location
Paint Color
2033D SERIES UPS
OWNERS / TECHNICAL MANUAL
30
24
AC INPUT
3 phase, 3 wire
480 V
+15% to -15% (-30% can be operated)
60 Hz (45.4Hz to 65Hz)
4% typ. at 100% load; 7% typ. at 50% load
STATIC BYPASS INPUT
3 phase, 3 wire
480 V
+/-10%
60 Hz
BATTERY
Lead Acid
Application Specific
480 Vdc
401 Vdc
240
AC OUTPUT
3 phase, 4 wire
120/208 V, 277/480 V
+/-1%
60 Hz
+/-0.05% in free running mode
0.8 nominal
0.8 - 1.0 lagging (within output kW rating)
2% typical THD at 100% Linear Load
5% typical THD at 100% non-linear load
+/-3% at 100% load step
+/-1% at loss/return of AC power
+/-3% at load transfer to/from static bypass
16.6ms
125% for 10 minutes,
1000% for 1 cycle
150% for 1 minutes
ENVIRONMENTAL
Forced Air
32゚F ~ 104゚F (0゚C - 40゚C)
Recommended 68゚F - 86゚F (20゚C - 30゚C)
5% ~ 95% Non Condensing
0 ~ 9000 feet No Derating
Indoor (free from corrosive gases and dust)
(PCB conformally coated for use in industrial environment)
Munsell 5Y7/1 (Beige)
MITSUBISHI ELECTRIC 2033D SERIES UPS
50
40
150% for 1 minute
(with bypass available)
Page Number:
1-12
80
64