Symbol explanation
Symbol
Explanation
ACCT1
AC current sensor
ACCT2
DCL
DC reactor
F01
F02
F03
F04
Fuse
F05
F06
F401
F402
MAIN BOX
LEV1, 3
Electronic expansion valve (Main circuit)
and
LEV2
Electronic expansion valve (Injection)
SUB BOX
MF1, 2
Fan motor
MS
Compressor motor
PSH1
High pressure sensor
PSL1
Low pressure sensor
R1, R2
Electrical resistance
21S4a
4-way valve
21S4b
THL
DC reactor temperature
Z22, 24, 25 Function setting connector
63H1
High pressure switch
72C
Electromagnetic relay (Inverter main circuit)
TH1~4,
9~11, 21
MAIN BOX
Thermistor
TH14, 15
Field-
<ELB1>
Earth leakage breaker
supplied
Inside the control box (front view)
Fan
Rec board
Inverter board
R1
R2
Noise filter
Inverter board
TB1
Control terminal block 2
Display setting
Control board display
Preset water temperature
Current water temperature *2
High pressure/Low pressure
*1 Select an item to be displayed by setting the switches.
*2 The current water temperature will be displayed according to the selection on the preset
water temperature display option.
*3 If an error occurs, a 4-digit error code, from a list of error codes in the table at right will
blink on the board and remote controller display. ([Error code] and [Error source address]
appear alternately on the remote controller display.)
*4 Definition of symbols in the "Error reset" column
... Errors that can be reset regardless of the switch settings
... Errors that can be reset if the remote reset setting on the unit is set to "Enable"
(factory setting)
Errors that cannot be reset if the remote reset setting on the unit is set to "Disable"
... Errors that cannot be reset
... Errors that will be automatically reset after the cause of the error is removed
*5 Power failure can be detected only when the switch setting "Automatic recovery after
power failure" on the unit is set to "Disable." (The default setting is "Enable.")
*6 Depending on the system configuration, the unit may come to an abnormal stop when the
communication error lasts for 10 minutes or longer. In this case, the error needs to be
reset by setting either SWS1 on the unit (PCB) or remote operation switch.
*7 This error code will appear when multiple errors occur that are reset in different ways and
when one or more of these errors have not been reset.
This error can be reset by turning off and then back on the unit's power.
*8 Remove the cause of the error before resetting the error.
Resuming operation without removing the cause may burst the heat exchanger.
*9 [Error code] and [Detail code] appear alternately.
Refer to the Installation Manual for detail codes.
Control board
IO
board
Transmission
power board
Control terminal block 1
Control board SW setting *1
SW6-5: ON
SW6-6: OFF
SW6-5: ON
SW6-6: ON
SW5-10: OFF
SW6-8: OFF
SW6-5: OFF
SW6-9: OFF
SW6-6: OFF
SW6-10: OFF
SW6-7: OFF
Error Codes
Error code
No.
(PCB *3)
A000
1
Unreset errors
4106
2
Power failure
A-P0
1102
3
Discharge temperature fault
AC61
1502
4
Compressor flooding
AdSH
2501
5
Water supply cutoff (Flow switch)
AFSA
1302
6
High pressure fault
AHP1
4102
7
Open phase
A471
0403
8
Serial communication error
1103
9
Shell temperature fault
1503
10
Heat exchanger freeze up
1505
11
Vacuum protection fault
4102
12
Open phase (T phase)
4106
13
Power supply fault
4115
14
Power supply frequency fault
4220
4225
,
,
15
Inverter bus voltage fault
4226
4230
4235
,
16
Inverter overheat protection fault
4236
4240
4245
,
17
Inverter overload protection fault
4246
4250
4255
,
18
IPM error (inclusive)/overcurrent relay trip *9
4256
5101
19
Discharge temperature thermistor error (TH1)
Compressor inlet temperature thermistor error
5102
20
(TH2)
5103
21
Shell temperature thermistor error (TH3)
Air-side heat exchanger refrigerant
5104
22
temperature thermistor error (TH4)
5109
23
Outside temperature thermistor error (TH9)
Inlet water temperature thermistor error
5116
24
(TH10)
Outlet water temperature thermistor error
5111
25
(TH11)
External water temperature thermistor error
5114
5115
26
,
(TH14, TH15)
Water-side heat exchanger refrigerant
5121
27
temperature thermistor error (TH21)
5201
28
High-pressure sensor fault
5202
29
Low-pressure sensor fault
5301
5305
30
ACCT•DCCT sensor fault/Circuit fault
,
6500
31
Communication error
6600
6603
Communication error
6606
32
(Simple multiple unit control)
6607
*6
6608
*6
6830
33
Address overlap
6831
34
Remote controller signal reception error 1
6832
35
Remote controller signal transmission error
6834
36
Remote controller signal reception error 2
7102
37
Incorrect setting of No.-of-connected-unit
7105
38
Address setting error
7113
7117
39
Model setting error
,
7130
40
Incompatible combination of units
49
Error reset *4
Unit side
Error type
(PCB)
SWS1
*7
*5
*8
*9
*9
*9
(
)
(
)
(
)
*9
Remote
controller
Operation
SW
(
)
(
)
(
)