Ambient Temperature

1.
2.
Ferrite cores that are snapped onto the shielded cabling may remove minor
disturbances. Large ferrite pieces that are snapped onto unshielded cabling and where
the wires go 2-4 times around the cores are approximately 5-25 times more efficient.
Ambient Temperature
The maximum ambient temperature for the operator panel is provided in the
specifications. The ambient temperature refers to the temperature in the device
cabinet which cools the operator panel's electronics.
In most cases, the ambient temperature for the operator panel is significantly higher
than the device cabinet's ambient temperature.
If the cabinet is tall and there are a number of heat-generating devices, the
temperature at the top of the cabinet is considerably higher than the temperature
increase that would be expected. All electronics are sensitive to heat. The lifespan of
38
Use an EMC cable gland or regular plastic cable gland, remove the outer jacket
and connect the shield to the installation plate with a 360° metal cable clamp.
Place the 24 V DC and communications cabling in one cable trunk/cable duct
and 230/380 V AC in another. If the cables need to be crossed, cross them at
90° only. Avoid combining the cabling for stronger 24 V DC outputs with
the communication cabling.
Operator
panel
30 °C outside
Section 7 Additional Installation Tips
Top
50 °C inside
Power
Power
Middle
45 °C inside
Power
Bottom
40 °C inside
Axial fan
120 x 120 mm
Airflow
3BSE069462-600 Rev D