< Characteristics setting for the AP module >
By combining this with the pre-alarm function installed as
standard, the two-step pre-alarms can be constructed.
For the AE630-SW low rating types, be sure to apply the
control power supply.
This cannot be combined with the WB type.
˜With the WS type
2nd pre-alarm
Time: Tp2 ( x T
)
L
Current (% of Iu)
Table 29
No.
Setting item
Symbol
2nd pre-alarm current
Ip2
2nd pre-alarm
Tp2
time
< N5 module >
LTD and pre-alarm characteristics of the neutral pole are 50% of the voltage pole.
However, STD and INST characteristics are the same as for the voltage pole (100%).
For the AE630-SW low rating types, be sure to apply the control power supply.
This cannot be combined with the WB type.
2nd pre-alarm
Current: Ip2
LTD time: T
L
12-25-50-100-150s (at Iu x 2)
2nd pre-alarm
Time: Tp2 (FLAT)
Characteristic setting range
0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 x Iu
0.5-0.6-0.7-0.8-0.84-0.88-0.92-0.96-1.0 x I
0.9-0.8-0.7-0.6-0.5-0.4-0.3 x T
- 5-10-15-20-30-40-60s
L
(x T
)
L
1
˜With the WM type
2nd pre-alarm
Time: Tp2 ( x T
)
L
Current (% of I
WS
WM
L
(FLAT)
2
2nd pre-alarm
Current: Ip2
LTD time: T
L
15-20-25-30-40-60 s (at I
x 1.2)
L
2nd pre-alarm
Time: Tp2 (FLAT)
)
L
Accuracy
Factory default value
±10%
WS
1.0
±5%
WM
±20%
0.9(x T
)
L
E-29