< Load current indicator LED >
The current value, which is used as a reference by the load
current indicator LED, varies depending on the applications
and relay types.
Table 22-1
Application
Relay type
classi cation
WS
WS1
General use
WS2
WS3
WM
WM1
Generator
protection
WM2
WM3
WB
WB1
Special purpose
WB2
WB3
WF
WF1
Protection
coordination
WF2
WF3
Note) When the "OVER" LED of WS, WB, or WF type or the "100%" LED of
WM type is lit, the current value is over the uninterrupted current. The
breaker will trip after the ETR set time is passed.
< Control power supply >
This is required for the trip cause indicator (LED, contact output), the measurement extension module, displays, etc. Over-cur-
rent and short-circuit protection is performed by the power supply CT energy, even if the control power supply is not available.
Applicable
Power
Rated voltage
supply
voltage range
(V)
type
(V)
P1
100-240 AC/DC
85-264 AC/DC
24-60 DC
18-72 DC
P2
100-240 AC
85-264 AC
P3
100-125 DC
85-138 DC
24-60 DC
18-72 DC
P4
P5
100-240 DC
85-264 DC
(1) Overcurrent protection is powered by the CT, which is built into the breaker. It
is operable regardless of the external power supply.
Ground fault protection (GFR) is also operable at 0.2 to 1.0 rated current (In)
settings, regardless of the control power supply.
(2) 6 contact outputs are set as below.
①LTD
②STD/INST
③G1/E1/AP
Self-hold type
Self-hold type
See the table below.
Dial setting
G1
TRIP side
Self-hold type
Self-hold type
ALARM side
Auto-reset type
Auto-reset type
With the power supply types P3 and P4, high-sensitivity relays are used for contact outputs. Because of that, contact outputs may
trigger chattering noise (approx. 1 ms of mis-outputs) at breaker opening/closing in some panel installation conditions. When us-
ing the product in a fast-response sequence, install a filtering circuit of a few milliseconds or perform double reading of samples.
E-22
Reference current
LED display
for LED display
OVER
Iu
100
Uninterrupted
80
current
60
%Iu
100
I
80
L
LTD pick-up
60
current
40
%I
L
OVER
Ir
100
Rated current
80
setting
60
%Ir
OVER
Ir
100
Rated current
80
setting
60
%Ir
Criterion
for power
Alarm output contacts
requiement
(VA)
15
10
15
6 contacts
10
6 contacts
15
6 non-contacts (SSR)
④PAL
⑤TAL
Auto-reset type
Auto-reset type
Self-hold type .... The output state is held until
E1
AP
Auto-reset type ... Output is reset upon returning
Auto-reset type
CAUTION
< Pre-alarm operation >
PAL LED will blink when the current exceeds the pre-alarm
current setting (Ip), and will be lit after 1/2 of the long time
lag (T
) is passed. The power supply type P3 to P5 will also
L
perform a contact output. For the operation time period, re-
fer to the characteristic curve.
Ip
Load current
PAL LED
PAL contact
output
Contact capacity (power supply type P3, P4)
Voltage (V)
AC
(50/60 Hz)
DC
Current capacity (power supply type P5)
Voltage (V)
AC
(50/60 Hz)
⑥ERR.
DC
Auto-reset type
it is reset.
to the normal condition.
Current
Lit
Blinking
ON
1/2 T
L
Time passed t
Current (A)
Resistance load
Induction load
cosø=0.4
cosø=1.0
L/R=0.7
240
1
120
1
125
0.1
0.05
30
1
Permissible peak
Steady current
ON resistance ( )
current at open/close
(A)
(A)
240
0.1
0.3
120
0.1
0.3
240
0.1
0.3
30
0.1
0.3
OFF
0.5
1
1
(Max.)
5
5
5
5