Outputs

11.1

Basis Unit Outputs

Basis Unit Outputs
SIMOCODE pro has a BU Outputs function block with there relay outputs. You can e.g.
switch, contactors or lamps via these Relay Outputs. For this, the inputs (plugs) of the
function block must be connected to the respective sockets (usually the QE. Contactor
controls of the control function).
The BU Outputs function block consists of:
● 3 plugs, corresponding to the Basic Unit outputs 1 to 3
● 3 relays
● Output terminals.
Application examples
● Control of the main Contactor in the motor feeder:
You can e.g. define which relay output is used for controlling the motor contactor in the
motor feeder. For this connect the desired relay output to the respective "QE" contactor
control of the control function.
● Lamp control for displaying operating states:
You can e.g. define which relay outputs are to be used for controlling the lamps/LEDs
displaying operating states of the motor (FAULT, ON, OFF, FAST, SLOW...).
For this, connect the desired relay output to the respective "QE..." contactor control of the
control function. The following are specially intended for controlling lamps and LED.
In addition to the status displays, the "QL..." lamp controls automatically signal via a 2 Hz
flash frequency.
● Test mode (QLE.../QLA lamp outputs are flashing)
● Unacknowledged fault (lamp output general fault QLS is flashing)
● Transfer of any other information, status information, warnings, faults etc. to the relay
outputs
● Lamp test: all QL outputs are activated for approx. 2 s.
In most cases, the outputs of the Basic Unit will be connected to the QE or QL outputs.
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001