Service Data - Statistical Data - Siemens SIMOCODE 3UF Programming And Operating Manual

Table of Contents

Advertisement

Online Settings and Displays

17.6 Service Data - Statistical Data

17.6
Service Data - Statistical Data
Service Data - Statistical Data
The following values are shown in the Motor section:
Motor
Motor operating hours
Number of overload trips
Number of starts
Permissible starts - actual value
Just one start possible
No start possible
Motor stop time
Motor stop time >
Time until test required
Test required
By specifying "Motor operating hours" and "Number of starts", for example, you can decide
whether motor and/or motor contactors should be replaced. To change these values enter a
new value in the right hand input field and press "Set". The value is accepted by the device.
Basic Unit
Device operating hours
Module time:
• Date
• Time
Time shift
Int. number of parametrizations
150
Range
0 to 1193046 h
0 to 65535
0 to 4294967295
0 to 255
See Warnings.
See Warnings.
0 to 65535 h
See Warnings.
0 to 255 w (weeks)
See Warnings, DM-F Test requirement.
Range
0 to 1193046 h
0 to 65535
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Description
indicate, how long voltage supply of
SIMOCODE pro was switched on.
Further information: Error Buffer-Error
Protocol.
Time information for the unbuffered
real time clock (only in conjunction
with SIMOCODE pro V PN basic unit).
The real time clock can be
synchronized using an
NTP server or via Target System ->
Command.
Configured time difference between
module time and UTC (Universal
Time Coordinated) (only in
conjunction with
SIMOCODE pro V PN basic unit)
SIMOCODE PRO V PN FDI

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simocode pro v pn fdi

Table of Contents