9.
REF
– (200TA/200TAL only) Set the reference (minimum) value for the
analogue output. [Default 0.000] Enter the displayed (scaled) value, below
which the analogue output will be at the minimum for the selected
voltage/current range.
Press select
←
through all four digits the decimal point position can be altered by pressing
increment ↑.
10.
FS
– (200TA/200TAL only) Set the full scale (maximum) value for the analogue
output. [Default 1000.] Enter the displayed (scaled) value, above which the
analogue output will be at the maximum for the selected voltage/current range.
Press select
←
through all four digits the decimal point position can be altered by pressing
increment ↑.
11.
DOUT
– (200TD/200TDL only) Set the digital frequency scaling factor.
This can be set between 0 (digital output off) and 0.5 (digital output frequency
equal to half of the input frequency). Values greater than 0.5 will be set to 0.5
automatically.
Press select
←
through all four digits the decimal point position can be altered by pressing
increment ↑.
12.
UPD
– Set the display and analogue/digital output update interval. [Default
1000]
Press increment
100
= 100ms (0.1s)
250
= 200ms (0.25s)
500
= 500ms (0.5s)
1000
= 1000ms (1.0s)
13.
LOCK
– (200TD/200TDL only) Lock settings
Press increment
NO
= Lock is disabled
YES
= Settings are locked and the unit will no longer enter set mode
To disable the lock, follow the procedure for entering set mode during the
"Init" stage on power-up.
to select digit and increment
to select digit and increment
to select digit and increment
↑
to select from the below options.
↑
to select from the below options.
↑
to change value. After cycling
↑
to change value. After cycling
↑
to change value. After cycling
9