Extra large orifice concealed pendent sprinklers

Advertisement

Quick Links

Model ELOC — 11.2 K-factor
Extra Large Orifice Concealed Pendent Sprinklers
Quick and Standard Response, Extended Coverage
General
Description
The TYCO Model ELOC, 11.2 K-fac-
tor, Extended Coverage, Light Hazard,
Extra Large Orifice Concealed (ELOC)
Pendent Sprinklers are decorative,
fast response solder type sprinklers
featuring a flat cover plate designed
to conceal the sprinkler. When limited
water pressure is available, the ELOC
is the best choice for architectural-
ly sensitive areas such as hotel lob-
bies, office buildings, churches, and
restaurants.
They are intended for use in automatic
sprinkler systems designed in accor-
dance with standard installation rules
(e.g., NFPA 13). The fast response
thermal sensitivity rating of the Mod-
el ELOC (TY5522) provides for a quick
response extended coverage (QREC)
rating up to an 18 ft. x 18 ft. coverage
area.
Each unit includes a Cover Plate As-
sembly that conceals the sprinkler op-
erating components above the ceiling.
The separable two-piece design of the
Cover Plate and Support Cup Assem-
blies allows installation of the sprin-
klers and pressure testing of the fire
protection system prior to installation
of a suspended ceiling or application
of the finish coating to a fixed ceiling.
They also permit removal of suspend-
ed ceiling panels for access to build-
ing service equipment without having
to first shut down the fire protection
system and remove sprinklers.
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cau-
tions with respect to handling
and installation of sprinkler sys-
tems and components. Improp-
er handling and installation can
permanently
damage
kler system or its components
and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
Also, the separable two-piece design
of the Sprinkler provides for 3/4 inch
(19,1 mm) of vertical adjustment to
provide a measure of flexibility with re-
gard to which the length of fixed pipe
drops to the sprinklers must be cut.
The Model ELOC Sprinklers are
shipped with a Disposable Protec-
tive Cap. The Protective Cap is tem-
porarily removed for installation, and
it can be replaced to help protect the
sprinkler while the ceiling is being in-
stalled or finished. The tip of the Pro-
tective Cap can also be used to mark
the center of the ceiling hole into plas-
ter board, ceiling tiles, etc. by gently
pushing the ceiling product against
the Protective Cap. When the ceiling
installation is complete the Protective
Cap is removed and the Cover Plate
Assembly installed.
As an option, the Model ELOC Pen-
dent Sprinklers may be fitted with a
silicone Air and Dust Seal (Ref. Fig. 4).
The Air and Dust Seal is intended for
sensitive areas where it is desirable
to stop air and dust travel through the
cover plate from the area above the
ceiling.
NOTICE
The Model ELOC Pendent Sprinklers
described herein must be installed
and maintained in compliance with
this document and with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any authorities having ju-
risdiction. Failure to do so may impair
the performance of these devices.
The owner is responsible for main-
taining their fire protection system
and devices in proper operating con-
dition. Contact the installing contrac-
tor or product manufacturer with any
questions.
a
sprin-
APRIL 2015
Worldwide
www.tyco-fire.com
Contacts
Sprinkler
Identification
Number
TY5522
TY5522 is a redesignation for C5522.
TFP250

Advertisement

loading
Need help?

Need help?

Do you have a question about the ELOC and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco ELOC

  • Page 1 Cap is removed and the Cover Plate (e.g., NFPA 13). The fast response Assembly installed. thermal sensitivity rating of the Mod- el ELOC (TY5522) provides for a quick As an option, the Model ELOC Pen- TY5522 response extended coverage (QREC) dent Sprinklers may be fitted with a TY5522 is a redesignation for C5522.
  • Page 2 * The 16’ x 16’ and 18’ x 18’ coverage areas are rated Standard Response when the Air and Dust sprinkler to activate and flow water. Seal (Fig. 4) is utilized. TABLE A MODEL ELOC 160°F (71°C) AND 212°F (100°C) PENDENT SPRINKLER (TY5522) HYDRAULIC DESIGN CRITERIA...
  • Page 3 Sprinkler as shown in Figure 3. The Model ELOC (TY5522) Pendent The ELOC must not be used in appli- Step 5. Replace the Protective Cap Sprinklers are UL and C-UL Listed for cations where the air pressure above (Ref.
  • Page 4 Deflector moves up and down freely. If FIGURE 4 the Sprinkler has been damaged and OPTIONAL AIR AND DUST SEAL FOR MODEL ELOC (TY5522) the Deflector does not move up and down freely, replace the entire Sprin- Figure 2. This air gap is necessary for Automatic sprinkler systems should kler assembly.