Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Model ELOC — 11.2 K-factor
Extra Large Orifice Concealed Pendent Sprinklers
Quick and Standard Response, Extended Coverage
General
Description
The Tyco
®
Model ELOC, 11.2 K-factor,
Model ELOC, 11.2 K-factor,
Extended Coverage, Light Hazard,
Extra Large Orifice Concealed (ELOC)
Pendent Sprinklers are decorative,
fast response solder type sprinklers
featuring a flat cover plate designed
to conceal the sprinkler. When limited
water pressure is available, the ELOC
is the best choice for architecturally
sensitive areas such as hotel lobbies,
office
buildings,
churches,
restaurants.
They are intended for use in automatic
sprinkler
systems
designed
accordance with standard installation
rules (e.g., NFPA 13). The fast response
thermal sensitivity rating of the Model
ELOC (TY5522) provides for a quick
response extended coverage (QREC)
rating up to an 18 ft. x 18 ft. coverage
area.
Each unit includes a Cover Plate
Assembly that conceals the sprinkler
operating
components
ceiling.
The
separable
design of the Cover Plate and Support
Cup Assemblies allows installation
of the sprinklers and pressure testing
of the fire protection system prior to
installation of a suspended ceiling or
application of the finish coating to a
fixed ceiling. They also permit removal
of
suspended
ceiling
panels
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its components
and cause the sprinkler to fail to
operate in a fire situation or cause it
to operate prematurely.
Page 1 of 6
access to building service equipment
without having to first shut down the
fire protection system and remove
sprinklers.
Also, the separable two-piece design
of the the Sprinkler provides for 3/4
inch (19,1 mm) of vertical adjustment
to provide a measure of flexibility with
regard to which the length of fixed pipe
drops to the sprinklers must be cut.
The
Model
shipped with a Disposable Protective
Cap. The Protective Cap is temporarily
removed for installation, and it can be
and
replaced to help protect the sprinkler
while the ceiling is being installed
or finished. The tip of the Protective
in
Cap can also be used to mark the
center of the ceiling hole into plaster
board, ceiling tiles, etc. by
pushing the ceiling product against
the Protective Cap. When the ceiling
installation is complete the Protective
Cap is removed and the Cover Plate
Assembly installed.
As an option, the Model ELOC Pendent
Sprinklers may be fitted with a silicone
above
the
Air and Dust Seal (Ref. Fig. 4). The Air
two-piece
and Dust Seal is intended for sensitive
areas where it is desirable to stop air
and dust travel through the cover plate
from the area above the ceiling.
NOTICE
The Model ELOC Pendent Sprinklers
for
described herein must be installed
and maintained in compliance with
this document and with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any authorities having ju-
risdiction. Failure to do so may impair
the performance of these devices.
The
owner
maintaining their fire protection system
a
n
d
d
v e
c i
condition. The installing contractor
or sprinkler manufacturer should be
contacted with any questions.
MARCH 2011
ELOC
Sprinklers
are
gentl y
WARNINGS
is
responsible
for
s e
n i
p
o r
p
r e
o
p
r e
t a
n i
g
Sprinkler
Identification
Number
TY5522
TY5522 is a redesignation of the C5522.
TFP250

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ELOC and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco ELOC

  • Page 1 Cap is removed and the Cover Plate area. Assembly installed. TY5522 Each unit includes a Cover Plate TY5522 is a redesignation of the C5522. As an option, the Model ELOC Pendent Assembly that conceals the sprinkler Sprinklers may be fitted with a silicone operating components above Air and Dust Seal (Ref.
  • Page 2: Technical Data

    SADDLE teria section.) Approvals for Air & Dust Seal: UL and C-UL Listed for use with the COMPRESSION SUPPORT Model ELOC (TY5522); however, all SCREW CUP WITH listed coverage areas are rated stan- ROLL FORMED dard response (Ref. Table A).
  • Page 3: Installation

    � ��c�o�y �pp��ie� finish� W�ench (Re�� Figu�e 3)� The W�Type �8 Criteria Sp�ink��e� W�ench is �o be �pp��ie� �o The ELOC must not be used in �he Sp�ink��e� �s shown in Figu�e 3� applications where the air pressure The �o�e�� ���� (TY55����) Pen�en�...
  • Page 4: Care And Maintenance

    Deflec�o� moves up �n� �own ��ee��y� I� FIGURe 4 �he Sp�ink��e� h�s been ��m�ge� �n� OPTIONAL AIR AND DUST SeAL FOR MODeL eLOc (TY5522) �he Deflec�o� �oes no� move up �n� �own ��ee��y�� �ep���ce �he en�i�e Sp�in� k��e� �ssemb��y� Do no� ���emp� �o mo��...