6. When connect to an Electrically operated damper, or take Operation monitor output
Power Supply
Monitor output
terminal (TM4)
Electrically
operated
damper
Lamp
7.When switching High/Low/Extra-Low fan speed externally (when CO
equipment is connected)
Using marketed CO
sensor, etc., make connection by inserting the optional remote display adaptor (PAC-SA88HA-E) in the
2
connector CN16 (High/Low selector) as shown by the figure.
CO
sensor, etc.
2
(When CO
increases: Closed)
SW1: High fan speed operation switch
(When closed: For High fan speed operation)
CO
sensor, etc.
2
(When CO dec
increases: Closed)
SW1: Low fan speed operation switch
(When closed: For Low fan speed operation)
SW1: Low fan speed operation switch
(When closed: For Low fan speed operation)
8.When switching By-pass externally
Establish the wire connection by inserting the optional remote display adaptor (PAC-SA88HA-E) in the connector CN16
(Ventilation mode selector).
SW1
SW1: Bypass ventilation operation switch
(When closed: For Bypass ventilation operation)
C-70
0
Contactor rating
9
Max 240 VAC, 2 A
24 VDC,
2 A
Min 220 VAC, 100 mA
5 VDC,
100 mA
Remote display
adaptor (Optional)
Lossnay
2
control board
PAC-SA88HA-E
Brown 1
SW1
Red 2
Orange 3
Yellow 4
Fan speed/
Green 5
Ventilation
mode selection
Not used. Insulate completely .
Max wiring length 10 m
Remote display
Lossnay
adaptor (Optional)
2
control board
PAC-SA88HA-E
Brown 1
CN16
Red 2
SW1
Orange 3
Yellow 4
Fan speed/
Green 5
Ventilation
mode selection
Not used. Insulate completely.
Max wiring length 10 m
Remote display
adaptor (Optional)
Lossnay
control board
PAC-SA88HA-E
Brown 1
CN16
Red 2
Orange 3
Y
ellow 4
SW1
Fan speed/
Green 5
Ventilation
mode selection
Not used. Insulate completely.
Max wiring length 10 m
Remote display adaptor
Lossnay
control board
(Optional) PAC-SA88HA-E
Brown 1
CN16
Red 2
Orange 3
Yellow 4
Fan speed/
Green 5
Ventilation
mode selection
Not used. Insulate completely.
Max wiring length 10 m
Connect the power supply cable from the Electrically operated
damper to 9 and 0 of the monitor output terminal block (TM4)
with reference to the wire connection diagram.
Operation monitor output with delay function 1 can be possible.
(Refer to function settings 6 (Refer to C-74) "Setting for TM4 90")
Note:
Don't tighten screws of
terminal block with a
torque larger than
0.5Nm. It could damage
the PCB.
Response times to external input signals are as shown in
the following table.
■ To force High fan speed externally
When SW1 is "ON", fan speed of the Lossnay will be set to
"High"(Extra-High) regardless of the remote control setting.
CN16
Use this in such a way that it ventilates at Low or Extra-Low
fan speed normally, and when the external sensor detects
contamination of indoor air, it changes to High (Extra High)
fan speed operation.
■ To force Low fan speed externally
When SW1 is "ON", fan speed of the Lossnay will be set to
"Low" regardless of the remote control setting.
Use this in such a way that it ventilates at High fan speed
normally, and when the external sensor detect that the indoor
air contamination is low, it changes to Low fan speed opera-
tion.
■ To force Extra-Low fan speed externally
When SW1 is "ON", fan speed of the Lossnay will be set to
"Extra-Low" regardless of the remote control setting.
Use this in such a way that it ventilates at High fan speed
normally, and when the external sensor detects that the
indoor air contamination is low, it changes to Extra-Low fan
speed operation.
* For the LGH-150RX
the Lossnay will be "Low".
With SW1 is "ON", the ventilation mode of Lossnay is changed
to the By-pass ventilation regardless of the setting on the
remote controller.
* When the outdoor air temperature drops lower than 8°C, it
changes to the heat exchanger ventilation. (Display of the
remote controller does not change.)
External Signal Response Time
Level Signal
Max. 7 sec.
Pulse Signal
Max. 200 msec
sensor or other
2
and LGH-200RX
types, fan speed of
5
5