Water cooled water chillers -modular-r134a-screw type
Hide thumbs Also See for SAMURAI Series:
Table of Contents

Advertisement

4 Troubleshooting
Troubleshooting by alarm code
01-01
Alarm code
Alarm stop reason
Startup circuit fails to self-hold after reception of operation signal, or upon automatic recovery from instant power failure.
PCB monitoring position
PCBc (CPU PCB) PCN15,PCN17
The connection and insertion of connector
PCN15 on PCBc (CPU PCB) is correct
The connection and insertion of connector
PCN17 on PCBc (CPU PCB) is correct
The insertion of the terminal of relay AR
Replace relay AR
05-05
Alarm code
Alarm stop reason
Power source connected locally is connected in reverse or in open phase.
PCB monitoring position
PCBd (I/O PCB) 3-phase support R, S, T
3-phase power source shows open or reverse
The connection and insertion of the
connector of 3-phase connectors R,S,T to PCBd
(I/O PCB) is correct
Power source of R,S,T connector shows
open or reverse phase
114
SMGB0120 rev.0 - 11/2017
Startup Circuit Failure
Yes
Yes
is
R
correct
Yes
R
Reverse/Open Phase
phase
No
No
Yes
Yes
No
No
No
No
Yes (Open reverse phase)
Revision of connections
Revision of connections
Revision of connections
Inspect power source and
voltage
Manual correction of
connection and insertion
Revision of wiring
Check PCBd (I/O PCB)