STRAINER/FILTER
DRIER
CONDENSER
EVAPORATOR
Figure 13: Santa Fe Advance
refrigeration system.
The evaporator operates in a flooded condition, which means that all the
evaporator tubes contain liquid refrigerant during normal operation. A flooded
evaporator should maintain constant pressure and temperature across the
entire coil, from inlet to outlet. The mixture of gas and liquid refrigerant
enter the accumulator after leaving the evaporator coil. The accumulator
prevents any liquid refrigerant from reaching the compressor. The compressor
evacuates the cool refrigerant gas from the accumulator and compresses it
to a high pressure and temperature gas to repeat the process.
7.2 Troubleshooting
No dehumidification, neither blower nor compressor run with fan switch AUTO.
1. Unit unplugged or no power to outlet, circuit breaker tripped.
2. Humidity control set to "Humid" setting.
3. Loose connection in internal wiring.
4. Humidity control is defective.
No dehumidification, compressor does not run but blower runs with fan
switch AUTO and humidity control turned to ON.
1. Defrost thermostat open, ambient temperature too low.
2. Loose connection in compressor circuit.
3. Defective compressor overload.
4. Defective compressor or compressor run capacitor.
Santa Fe Advance Owner's Manual
COMPRESSOR
CAPILLARY
TUBES
ACCUMULATOR
# %
/
=8
"
2$4
2$4
2$4
6
2$4
Figure 14: Wiring diagram.
5
5
3 $
2$4
11