Auxiliary 24 VDC output
Output voltage ................................................................................................18 V to 28 V (nominal of 24 VDC)
Maximum current ..................................................................................................................................... 250 mA
Recommended cable................................................................................................Stranded 2-wire of 1.5 mm²
Power Supply
Mains voltage (230) .........................................................................................230 VAC 50 Hz / 110 VAC 60 Hz
Voltage tolerance.............................................................................................................................+10% / -15%
Power supply input ................................................................................................................................. 24 VAC
Resetable 24 VDC output
Maximum commutation power ................................................................................................................ 100 mA
Reset time ........................................................................................................................................... 3 seconds
Fuses
FP402, FP404 mains fuse for 230 VAC (F12).................................................................... 0.5 A (T) 250V (5ST)
FP402, FP404 mains fuse for 110 VAC (F11)....................................................................... 1 A (T) 250V (5ST)
FP408, FP412, FP416 mains fuse for 230 VAC (F12) .......................................................... 1 A (T) 250V (5ST)
FP408, FP412, FP416 mains fuse for 110 VAC (F11) .......................................................... 2 A (T) 250V (5ST)
Sounder fuse 1 (F1)...........................................................................................................0.3 A (T) 20 mm HCR
Sounder fuse 2 (F2)...........................................................................................................0.3 A (T) 20 mm HRC
Auxiliary 24 V fuse (F3) .....................................................................................................0.3 A (T) 20 mm HCR
24 V Reset fuse (F4)..........................................................................................................0.1 A (T) 20 mm HRC
Battery fuse FP402 & FP404 (F5) ........................................................................................2 A (T) 20 mm HCR
Battery fuse FP408, FP412 & FP416 (F5)............................................................................5 A (T) 20 mm HCR
Current in stand-by status
FP402/FP404 ............................................................................................................................................ 75 mA
FP408/FP412/FP416 .............................................................................................................................. 137 mA
Current in alarm status
FP402/FP404 .......................................................................................................................................... 162 mA
FP408/FP412/FP416 .............................................................................................................................. 247 mA
Battery charger
Output voltage ................................................................................................................ 27.6 V nominal at 20°C
Compensation........................................................................................................................................ -3 mV/ºC
Load current
FP402/FP404........................................................................................................................................... 125 mA
FP408/FP412/FP416 ............................................................................................................................... 350 mA
Batteries
FP402/FP404...................................................................................................2 units of 12 V 2.6 Ah (lead type)
FP408/FP412/FP416 .......................................................................................... 2 units of 12 V 7 Ah (lead type)
22
FP400 Series Installation Manual

Advertisement

Table of Contents
loading

Table of Contents