Master Modules - GE ARITECH FP400 Series Installation Manual

Conventional microprocessor controlled fire detection and alarm panels
Hide thumbs Also See for ARITECH FP400 Series:
Table of Contents

Advertisement

Figure 21: Active EOL configuration
Active EOL active
Figure 22: Connection of a diode in an active end-of-line installation
Zone
The active end-of-line module is optional.
2.3.3 Configuration for remote reseting
Remote Reset mode changes the normal function of the class change input. If the class
change input is activated, then the reset will be activated. If the class change input
remains activated a fault is shown activating the fault relay.
Use DIP switch 8 to activate this mode (see Figure 23 Remote reset configuration).
Figure 23: Remote reset configuration
Remote reset active

2.4 Master modules

Two versions of the master module are available: a master module with 24 VDC outputs
and a master module with potential free relay outputs.
16
Active EOL inactive
Schottky
diode BAT43
You may activate either active end-of-line resistors or remote reset mode.
You may not activate both simultaneously.
Remote reset inactive
Refer to individual module installation guides for complete product features
and installation details.
Active end–
of-line
FP400 Series Installation Manual