Page 1
I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Bypass-Isolation Automatic Transfer Switches Zenith ZBTS T-series, 100 - 1200 A...
Page 2
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
Page 3
HAZARD OF EQUIPMENT with the transportation company, and no- OVERTURNING tify your local ABB sales office. When moving with a fork lift, do not re- move the shipping package until the de- Do not remove the shipping package until ready to install the Bypass-Isolation Auto- vice is in its final location.
Page 4
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — Read these safety instructions carefully before using this product! Danger Warning...
Page 5
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — Installation and Operating Instruction OPER ATING INSTRUCTIONS, Bypass-Isolation ZENITH ZBTS T-SERIES...
Page 6
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — Operating Instruction Bypass-Isolation Automatic Transfer Switches, Zenith ZBTS T-series 100-1200A PART 1...
Page 8
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3 HMI, menu tree 3.3.1 Start Menu 3.4 Description of Basic Functionality 3.4.1 How to draw out the switch to Test...
Page 9
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 6. Technical Data 6.1 Technical Data of Bypass-Isolation Transfer Switches 6.1.1 I/O Contacts, Default Settings / Bypass-Isolation Automatic...
Page 10
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
1. Introduction Operating instruction part of the manual The safe operation of your Bypass-Isola- (Chapters 1...6) describes the basic oper- tion Automatic Transfer Switch is ABB’s ation of the Bypass-isolation automatic focus. The proper storage, installation, transfer switches Zenith ZBTS T-series operation and maintenance will help in- 100-1200A, manufactured by ABB.
ABB representative for Non-US war- hardware and software systems. ranty terms and conditions. ABB Zenith assumes no obligation of no- For support in the United States, contact tice to holders of this document with re- service team at: +1 800 637 1738 or spect to changes subsequently made.
Strict procedures ensure firstclass product quality. Product Rating / Applicable Standards For UL 1008 ‘withstand’ and ‘close on short circuit’ ratings, refer to ABB publica- tion number 1SCC303020C0201. Product Serial Number Please have the serial number available when communicating about the By- pass-Isolation automatic transfer switch.
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 1.4 Definitions Automatic transfer switches Source 1, relate to a Normal Power Source Ekip Electronic accessories / Ekip-modules;...
ATS is disabled or removed from service. Bypass-Isolation Automatic Transfer Switch, consist of two ABB Zenith Auto- matic Transfer Switches (TruONE ATS) from 100A up to 1200A, are used to pro- vide a continuous source of power for critical loads.
Page 16
The ATS Warning Due to hazardous voltage and current, ABB switch in the lower switch module is al- recommends that ABB certified technician or ways a draw-out version that includes an qualified electrician perform the installation and maintenance.
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 2.1 General Overview 4 3 2 Ground Terminal Fixed Bypass in the picture (alternative: Bypass is draw-out...
Page 18
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Operation instruction HMI unit on the door, Level 4 (touch) for configuration and automatic operation, operation of the Bypass switch...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 2.2 Main and Control Connections 2.2.1 Main Connections The top module of enclosure is for cable lugs for Source 1, for Source 2 and for...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N The upper switch is the Bypass switch. It can be fixed or draw-out version.
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 2.3 HMI HMIs are the control interfaces (Human touch screen for both switches Bypass Machine Interface), available as level 4 for and ATS.
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 2.4 Bypass and ATS Switches, Features Features Level 4 controls (TOUCH) LOAD...
Page 23
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Features Level 4 controls (TOUCH) LOAD AUTO Override momentary...
Page 24
For applications Mains - Mains Mains - Generator Contact ABB for applications with smaller than 20 kVA gensets Includes support for redundant module — Table 2.1 ATS feature comparison, main features - but not limited to - in the table above...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 3. Operating — 3.1 LED Functionality in HMIs LED functionality in HMIs is similiar for both Bypass and ATS switches.
Page 26
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Bypass Lamp Auto load load time test...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 3.2 Using the Control Interface HMI 3.2.1 Keypad Keypad functionality in HMIs is similiar for both Bypass and ATS switches...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 3.3 HMI, menu tree Password The small icons in Switch Overview -pages are:...
Page 29
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Alarm List To Define the Home Page 11:06 Alarm List Switch Overview...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3.1 Start Menu Overviews Analog Meters Switch Overview —...
Page 31
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 3.3.1.2 Bypass System Overview 10:55 Bypass System Overview LOAD AUTO...
Page 32
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3.1.3 Main Menu Overviews Analog Meters Overviews Switch Overview...
Page 33
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Operation *Default Alarm Reset Reset any active switch control alarms (open I failure, close I failure, open II failure, close II failure) Bypass Time Delay Bypass any currently running time delay...
Page 34
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.3.1.4 Analog Meters Overviews Analog Meters Switch Overview 0.0V...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 3.4 Description of Basic Functionality The system provides the ability to with- tion allows also the use of the HMIs on draw the ATS for test and / or mainte-...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Warning ATS and Bypass switch "OFF" Position keys are always enabled.
Page 37
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 The switch and HMI of ATS has now lost 00:34 the power, the ATS is completely discon- Switch Overview...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.4.2 How to use the Draw-out 05:11 Mechanism to rack out the Switch Switch Overview...
Page 39
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 NOTE! In Test location all electrical opera- While the ATS is racked out to the Test lo- tions are allowed.
Page 40
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N In CONNECTED location In CONNECTED location, Push button pushed, Push button returns, TEST location reached, Racking in/out tool inserted, ready to start rotation Push button pushed agen, Racking in/out tool...
Page 41
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 HMI of Bypass: HMI of ATS: Page “Bypass System Overview”...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 3.4.3 To Reconnect ATS Switch NOTE! Remember that ATS must be in Reconnecting the ATS switch after main- OFF-position, when moving in/out.
Page 43
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Operate Bypass switch to OFF- 00:14 position as shown in the Fig.
Page 44
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 4. Electronic Accessories NOTE! It is still possible to add two pieces of Ekip modules to the fixed Bypass switch Warning Hazardous voltage may be present within the...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 4.1 Auxiliary Power Supply Module OXEA1 The auxiliary power supply module, type ferrule;...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 4.2 Ekip Supply Module The Ekip Supply is a power supply acces- 4.2.2 Signallings sory module.
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 4.3 Ekip Signalling 2K -module The Ekip Signalling 2K-3 is a signalling ac- Component Characteristics...
Page 49
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Settings (*Default) Description Modules (Optional modules) Ekip Signalling 2K -3 I 11/12, I 21/22, I 31/32...
Page 50
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Settings (*Default) Description Modules (Optional modules) (continued) O 11/12, O 21/22, O 31/32 Function* Function No...
Page 51
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Test Modules (Optional modules) Ekip Signalling 2K-1 / -2 / Auto Test —...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 4.3.3 Signals and inputs/outputs of Green LED for signalling the physical Ekip Signalling 2K -module...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 5. Troubleshooting Warning Danger Any troubleshooting should be conducted by Hazardous voltage may be present.
Page 54
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Alarms, continued from previous page Message Fault Action...
Page 55
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Alarms, continued from previous page Message Fault Action...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 5.2 Warnings Message Reason S1 and S2 not in sync Voltage sources are not synchronized...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 5.3 Information Message Description Invalid Date Date not set Test on Load...
Page 58
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
Page 59
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 6. Technical Data 6.1 Technical Data of Bypass-Isolation Transfer Switches Bypass-Isolation Transfer Switch, Power Circuit Value Rated operational voltage U, three phase...
Page 60
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Automatic Transfer Switch, I/O Contacts Cabling Rating / Remark Generator start/stop...
Page 61
Table 6.4 Automatic transfer switches: Specified technical data of operating times Type peak 500 V [kA] 100...1200 Iq 100 kA rms. OFA_1600 A gG 80.8 9900 OFA_1250 A aM 91.3 11600 Iq 85 kA rms. ABB T7L1600_ 111.6 44900 — Table 6.5 Automatic transfer switches: Rated conditional short-circuit values...
Page 62
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 6.1.1 I/O Contacts, Default Settings / Bypass-Isolation Automatic Transfer Switch These settings are for internal use only, these settings cannot be changed.
Page 63
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 6.2 Circuit Diagrams The following pages contain simplified circuit diagrams for Bypass-Isolation au- tomatic transfer switch products.
Page 65
MATERIAL NORM NET WEIGHT VOLUME AREA CREATED MODIFIED APPROVED ECN NUMBER ECN DATE CONCERNING DRAWING FILE ORGANIZATION DEPARTMENT TOLERANCES ABB Oy, Smart Power FIELSP TYPE SCALE FORMAT LANGUAGE SHEET TITLE (FI) 1 : 1 EN/FI REV. TITLE (EN) DOC. NO.
Page 67
2021-06-08 Jonna Ojala 2021-06-08 Jonna Ojala 2021-06-08 Timo Jokiniemi ECN NUMBER ECN DATE CONCERNING DRAWING FILE TruBypass ZSDD040-120-1-Z31 ORGANIZATION DEPARTMENT TOLERANCES ABB Oy, Smart Power FIELSP TYPE SCALE FORMAT LANGUAGE SHEET TITLE (FI) 1 : 1 EN/FI REV. TITLE (EN) DOC.
Page 68
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
Page 69
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — Installation Instruction Bypass-Isolation Automatic Transfer Switches Zenith ZBTS T-series 100-1200A 7.
Use a vacuum cleaner to remove all are installed and properly fastened. debris caused by transport or installation. Each ABB Zenith Bypass-isolation auto- matic transfer switch is factory wired and tested. A complete information package Warning is furnished with each switch which...
Proper lifting equipment must be used to de-energised. mount the Bypass-isolation transfer switch cabinet into place (Note: The weight of 4-pole Standard ABB Zenith By- pass-Isolation automatic transfer switch Warning is 775kg/1709 lb, see the weight informa- Before drilling conduit entry holes or any ac- cessory mounting holes, cover and protect tion in Dimension Drawings ).
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 7.1.2 Lifting the Draw-out Switch Proper lifting equipment must be used to lift the draw-out switch for inspection and servicing (Note: eg.
Page 73
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 – Fig. 7.3 Lifting the switch must be performed using an adequate lifting means. The numbers in the picture will tell the different stages of the task.
7.2.1 Power Connections with Screw Type Terminals (as standard) Danger Hazardous voltage may be present. Only an au- ABB Zenith Bypass-isolation automatic thorised electrician may perform the electri- cal installation and maintenance of OX_ auto- transfer switches are supplied with UL matic transfer switches.
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 7.2.2 Power Connections with Compression Lugs (option) ABB Zenith Bypass-isolation automatic transfer switches are supplied as an op- tion for cable lug connections. Below the bolt size and tightening torque for com- pression lugs.
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 7.2.3 Ground Connections with Screw 7.2.4 Neutral Connections with Screw Type Terminals Type Terminals ABB Zenith Bypass-isolation automatic ABB Zenith Bypass-isolation automatic transfer switches are supplied with UL transfer switches are supplied with UL listed solderless screw-type ground ter- listed solderless screw-type neutral termi- minal as optional choice.
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 7.2.7 Engine/Generator Start Control possible to the connectors, see the con- Connections duit area in picture below.
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 7.2.8 Customer Connections, I/O Signals Customer Customer Connections: Connections: Output O1 External supply In ABB Zenith Bypass-Isolation Automatic for Ekip Connections for Fixed and Modules Transfer Switches there are some I/O Draw-out switch connections, which are available for cus- tomer use, if needed.
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 8. Mounting of Accessories More information, see animation: Installation of accessories - TruONE™...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 8.1.1 Mounting of Ekip –modules to the fixed Bypass switch —...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 8.2 Wiring routes of I/O-connections / Ekip -modules inside the cabinet Once all the afterwards added or factory Continue the connections on the...
Page 83
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — Maintenance Bypass-isolation automatic transfer switches Zenith ZBTS T-series 100-1200A 9.
9. Maintenance — 9.1 Maintenance Principle Warning Warning Due to hazardous voltage and current, ABB Hazardous voltage may be present. Discon- recommends that ABB certified technician or nect all power sources before performing qualified electrician must perform the instal- work inside the Bypass-isolation automatic lation and maintenance.
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 9.2 Useful Tips for Service Situations These operations are recommended for If the door needs to be opened for service maintenance use only.
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 9.2.2 Release the Locking Solenoid solenoid terminals are situated on the The locking solenoids are located behind back side of the control plate.
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 NOTE! The rack in / out mechanism works only when the switch is in the OFF posi- tion and the other switch is in the I / II position.
(with as many Further information on Ekip Signalling LEDs, giving a total of twenty LEDs). 10K is available from the web site http:// www.abb.com/abblibrary/ DownloadCenter/, in particular in the manual 1SDH001318R0002. — Fig. 9.5 Ekip Signalling 10K module...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Connections The module must be mounted on a DIN rail, and connected by wiring the connec- X14: 5 (+24V DC) tors on the module.
Page 90
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Position Description KS01, Pins of the output contact O S01. KS02 KS03, Pins of the output contact O S02.
Page 91
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 Position Description Power LED, green. The possible states are: •...
Page 92
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Position Description I S01 Signalling LED of the input I S01 physical status, green.The possible states are: •...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 9.3.3 Communication Connectors The communication connectors are posi- tioned on the upper side of the module.
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N 9.3.5 DIP switch configuration when installing Ekip Signalling 10K module At installation, the module must be con- figured to communicate via Local Bus or...
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 9.5 Heater Heater is used for prevention of conden- is turned "ON".
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — 9.6 Meter The multifunction power meter is an ac- Features: cessory, it is designed to be used in elec- •...
Fuse Disconnector is needed for OVR Surge Protection Device. The recom- factory. mended type is: 9.7.1 Surge Protection Device OVR • ABB Fuse Disconnector E93/50 OVR range is designed to prevent electri- - 2CSM277962R1801 E93/50 cal systems and equipment against tran-...
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 9.7.3 Integrated SPD, Type TPME_ 9.7.3.1 Other Features of TPME_ •...
Page 100
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
Page 101
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1 — Dimension drawings Bypass-isolation automatic transfer switches Zenith ZBTS T-series 100-1200A 10.
Page 102
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N — 10. Dimension drawings Fig.
Page 103
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1...
Page 104
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Fig. 10.2 ZS 30-1200, dimension drawings, cabin inside...
Page 105
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1...
Page 106
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N Fig. 10.3 ZS 30-1200, Adapter bay, cable entry from bottom...
Page 107
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1...
Page 108
Zenith ZBTS T-series 100-1200A, I N S TA L L AT I O N A N D O P E R AT I N G I N S T R U C T I O N...
Page 109
3 4 Z B T S _ 3 0 - 1 2 0 0 A r e v. A / 1 S C C 3 0 3 0 4 3 M 0 2 0 1...