Huawei SUN2000 Series User Manual page 96

Hide thumbs Also See for SUN2000 Series:
Table of Contents

Advertisement

SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
Seires
User Manual
Alarm
Alarm Name
ID
2031
Phase Wire
Short-Circuited
to PE
2032
Grid Loss
2033
Grid
Undervoltage
Issue 03 (2021-09-30)
Alarm
Cause
Severity
Major
Cause ID=1
The impedance of the
output phase wire to PE is
low or the output phase
wire is short-circuited to
PE.
Major
Cause ID=1
1. The power grid
experiences an outage.
2. The AC circuit is
disconnected or the AC
switch is off.
Major
Cause ID=1
The grid voltage is below
the lower threshold or the
undervoltage duration has
exceeded the time that
triggers LVRT.
Copyright © Huawei Technologies Co., Ltd.
8 Maintenance
Troubleshooting Suggestions
Check the impedance of the
output phase wire to PE,
locate the position with lower
impedance, and rectify the
fault.
1. The alarm is automatically
cleared after the power
grid is restored.
2. Check whether the AC
circuit is disconnected or
the AC switch is off.
1. If the alarm occurs
occasionally, the power grid
may be abnormal
temporarily. The inverter
automatically recovers
after detecting that the
power grid becomes
normal.
2. If the alarm occurs
frequently, check whether
the power grid voltage is
within the acceptable
range. If not, contact the
local power operator. If yes,
modify the grid
undervoltage protection
threshold through the
mobile app, SmartLogger,
or network management
system (NMS) with the
consent of the local power
operator.
3. If the fault persists for a
long time, check the AC
circuit breaker and AC
output power cable.
89

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

This manual is also suitable for:

Sun2000-196ktl-h3Sun2000-200ktl-h3Sun2000-215ktl-h3

Table of Contents