Panasonic CZ-64ESMC3 Installation Instructions Manual page 20

System controller
Hide thumbs Also See for CZ-64ESMC3:
Table of Contents

Advertisement

Setting
Item
code
Flap setting
06
Disables switching operation of airfl ow direction and disables the airfl ow
display.
Alarm output delay function
07
Delays the relay output ON when an alarm occurs.
Password auto lock
09
Locks the password during no operation when the password is temporarily
unlocked.
Screen auto off
0A
Clears the LCD display during no operation.
Peak cut function
0C
Schedule peak cut/Schedule energy saving/External input peak cut
Switches among the 3 functions.
Temp display setting
0E
Set the type of temperature display.
Password change
2F
Enables changing the password for the password setting function.
Display of operation lock cancelling method
Set whether to display the operation lock cancelling method on the lock
36
screen while operation is locked. (For the lock screen, see the “Part
Names” section in the Quick Reference.)
Number-of-controlled-units mode
In combination of the item code 03 “All/Zone mode” and the item code 05 “Central
control/Remote control mode”, the following
All mode
Zone 1 mode
Zone 2 mode
Zone 3 mode
Zone 4 mode
20
(EN)
(continued)
Set contents
Central control/Remote control mode
Central control
mode
Disabling the setting
function can be
used.
All central control
Zone 1 central
control
Zone 2 central
control
Zone 3 central
control
Zone 4 central
control
to
modes can be set.
Remote control mode
Disabling the setting function
cannot be used.
• The Prohibit R/C setting is
disabled.
All remote control
Zone 1 remote control
Zone 2 remote control
Zone 3 remote control
Zone 4 remote control
*Factory default
Set data
• 0000: Display and
operation enabled*
• 0001:Display and
operation disabled
• 0000: No delay*
• 0001 to 0015
• 0001: 1 min,
0015: 15 min
(1-minute interval)
• 0000: Auto lock not set
• 0001: 5 min
• 0006: 30 min
(5-minute interval)*
• 0000: Not set*
• 0001: 30 min
• 0000: Schedule peak cut*
• 0001: Schedule energy saving
• 0002: External input peak cut
• 0000: °C*
• 0001: °F
• 0000 to 9999:
• 0000: *
• 0000: Displayed*
• 0001: Not displayed
Control target
Group
Zone
1 to 64
1 to 4
1 to 16
1
17 to 32
2
33 to 48
3
49 to 64
4