Download Print this page

System With Multiple Hbcs - Mitsubishi Electric PURY-M200YNW-A1 Service Handbook

Hide thumbs Also See for PURY-M200YNW-A1:

Advertisement

[2-7 Example System with an MA Remote Controller ]
2-7-6

System with Multiple HBCs

(1) Sample control wiring
Move the male connector
from CN41 to CN40
SW5-1 OFF ON
OC
HB
2
51
52
TB3
TB3
M1M2
M1M2
TB7
M1M2
S
To be connected
Leave the male
connector on
CN41 as it is.
SW5-1 OFF ON
OC
HB
3
2
53
54
TB3
TB3
M1M2
M1M2 S
TB7
M1M2
S
To be left
unconnected
Note1
System
controller
A B S
(2) Cautions
1)
ME remote controller and MA remote controller cannot both be con-
nected to the same group of indoor units.
2)
No more than 2 MA remote controllers can be connected to a group
of indoor units.
3)
Do not connect the terminal blocks (TB5) on the indoor units that are
connected to different outdoor units with each other.
4)
Replacement of male power jumper connector (CN41) must be per-
formed only on one of the outdoor units.
5)
Short-circuit the S (shield) terminal of the terminal block for the cen-
tral control unit (TB7) and the ground terminal (
unit whose power jumper was moved from CN41 to CN40.
6)
When the number of the connected indoor units is as shown in the
table below, one or more transmission boosters (sold separately)
are required.
To connect two transmission boosters, connect them in parallel.
(Observe the maximum number of connectable indoor units that are
listed in the specifications for each outdoor unit.)
When the W/WP/WL200 and
W/WP/WL250 models are not in-
cluded in the connected indoor units
When the W/WP/WL200 and
W/WP/WL250 models are included
in the connected indoor units
The table above shows the number of transmission boost-
ers that is required by the system with four HBCs. For each
HBC added or subtracted, subtract or add two indoor units.
Refer to the DATABOOK for further information about how
many booster units are required for a given system.
7) When a power supply unit is connected to the transmission
line for centralized control, leave the power jumper connec-
tor on CN41 as it is (factory setting).
BS_02_L
Group
Group
IC
IC
IC
1
1
2
01
02
04
TB5
TB15
TB5
TB15
TB5
S
M1M2
S
1 2
M1M2
S
1 2
M1M2
S
m2
A1 B2
MA
m3
L22
Group
Group
IC
IC
IC
1
1
2
03
05
06
TB5
TB5
TB15
TB5
TB15
TB15
M1M2
S
1 2
M1M2
S
1 2
M1M2
S
1 2
m1
A1 B2
A1 B2
MA
MA
*1 When only the LM adapter is connected, leave SW5-1 to OFF (as it is).
*2 LM adapters require the power supply capacity of single-phase AC 220 - 240V.
) on the outdoor
Number of transmission booster
(sold separately) required
1 unit
2 units
25 - 50 units
-
19 - 37 units
38 - 50 units
L12
Group
HS1
IC
IC
2
2
1
1
2
07
08
57
57
TB15
TB3
TB5
TB15
TB5
TB15
1 2
M1M2
S
M1M2
S
1 2
M1M2
S
1 2
A1 B2
A1 B2
MA
MA
Group
HS1
IC
IC
3
1
1
1
09
10
59
TB3
TB5
TB15
TB5
TB15
M1M2
S
M1M2
S
1 2
M1M2
S
1 2
A1 B2
MA
Numbers in the square indicate port numbers.
Connection to HBC
Interlock operation with the ventilation unit
(3) Maximum allowable length
1) Indoor/outdoor transmission line
Maximum distance (1.25mm
L12 200m [656ft]
L22 200m [656ft]
The maximum piping length between OC and HB is 150 m.
2) Transmission line for centralized control
L31+L32
200m [656ft]
3) MA remote controller wiring
Maximum overall line length
(0.3 to 1.25mm
m1 200m [656ft]
m2+m3 200m [656ft]
4) Maximum line distance via outdoor unit
2
(1.25mm
[AWG16] or larger)
L32+L31+L12
L32+L22
1000 m [3280ft] (500 m [1640ft])
L12+L31+L22
*1 If a given system includes one or more unit or remote
controller that does not support the maximum allow-
able cable distance of 1000 m [3280 ft], the maximum
allowable cable distance in the system will be 500 m
[1640 ft]. Refer to the latest catalog for information on
which units and remote controllers support the maxi-
mum allowable cable distance of 1000 m [3280 ft].
Group
HS2
IC
IC
2
1
1
2
11
12
61
TB3
TB5
TB15
TB5
TB15
TB5
M1M2
S
M1M2
S
1 2
M1M2
S
1 2
M1M2
A1 B2
MA
LC
14
TB5
M1M2
S
2
[AWG16] or larger)
2
[AWG22 to 16])
1000 m [3280ft] (500 m [1640ft])
1000 m [3280ft] (500 m [1640ft])
LC
13
S
*1
*1
*1
21
chapter 2 -

Hide quick links:

Advertisement

loading