[8-14 HBC Maintenance Instructions (Applicable to main and sub HBCs) ]
8-14 HBC Maintenance Instructions (Applicable to main and sub
HBCs)
8-14-1
Valve Block
VB3 (valve block) is driven by the pulse signal from the VB board and are controlled by a stepping motor.
1) VB board and valve block (VB3)
Valve block
4
3
Limit signal
2
(Opening
"0" signal)
1
2) Pulse signal output and valve motion
Output (phase)
number
4
5
7
8
If the LEDs (VB3a-VB3p) on the VB board are lit, check the relevant valve blocks for loose connectors and faulty wiring. Make
sure that the valve blocks are properly controlling the refrigerant flow.
If the LED is unlit, check all valve blocks for proper operation.
If the problem persists after taking the above measures, replace the circuit board.
3) Opening and closing of the valve
BS_08_L
5
M
6
6
7
8
Output status
1
2
3
ON
ON
OFF
OFF
ON
ON
OFF
OFF
ON
ON
OFF
OFF
Cooling
Closing
the valve
Opening
the valve
0
Circuit board
8
7
6
5
4
3
2
LED
1
GND
4
OFF
When valve opens (0 → C800 or H800): 4 → 3 → 2 → 1
OFF
When valve closes (C800 or H800 → 0): 1 → 2 → 3 → 4
ON
ON
Heating
Opening
the valve
700
800
900
Number of pulses
12V
12V
Microcomputer
Closing
the valve
1600
chapter 8 -
127